Omron KP100G Technical Manual page 41

Grid connect photovoltaic inverter
Hide thumbs Also See for KP100G:
Table of Contents

Advertisement

KP100G
LCD(Data Logger) Messages
Operating
In English
conditions
Normal Working Status
Shown in "Status" row on the display
Power off
Standby
STATUS:STANDBY
Initialization &
STATUS:Waiting
waiting
STATUS:CHECKING
Check grid
xxxs
Feeding grid,
STAUS:Normal
MPPT
Waiting for
STATUS:RECONNECT
reconnect to grid
xxxs
FAULT
STATUS:FAULT
Monitoring Parameters
Information on display
Instantaneous Input
Pdc:xxxx/xxxx/xxxxW
power
Instantaneous
Pac:xxxxxW
Output power
Accumulated
Etot:xxxxxxxxx.xkWh
energy information
3-phase Grid
Vac:xxx.x/xxx.x/xxx.xV Uac:xxx.x/xxx.x/xxx.xV Vac:xxx.x/xxx.x/xxx.xV
voltage
Grid frequency
Frequency:xx.xHz
Feeding current
Iac:xx.x/xx.x/xx.xA
PV array voltage
Vdc:xxx/xxx/xxxV
PV array current
Idc:xx.x/xx.x/xx.xA
Daily Energy
Etoday:xxx.xkWh
Working Hour
H-total:xxxxxxhr
Internal
TEMPERATURE:xx.xºC Temperatur:xx.xºC
Temperature
In German
In Spanish
Status:Bereitschaft
ESTADO:EN ESPERA
Status:Warten
ESTADO:PREPARADO PRONTO
ESTADO:CHEQUEO
Status:Netz-Prüf xxxs
xxxs
Status:Normalbetriebe
ESTADO:NORMAL
ESTADO:RECONEX
Status:Kontakt xxxs
xxxs
Status:Fehler
ESTADO:ANOMALIA
Pdc:xxxx/xxxx/xxxxW
Pdc:xxxx/xxxx/xxxxW
Pac:xxxxxW
Pac:xxxxxW
E-tot:xxxxxxxxx.xkWh
Etot:xxxxxxxxx.xkWh
Frequenz:xx.x Hz
Frecuencia:xx.x Hz
Iac:xx.x/xx.x/xx.xA
Iac:xx.x/xx.x/xx.xA
Udc:xxx/xxx/xxxV
Vdc:xxx/xxx/xxxV
Idc:xx.x/xx.x/xx.xA
Idc:xx.x/xx.x/xx.xA
E-Heute:xxx.xkWh
Edia:xxx.xkWh
H-total:xxxxxxhr
Htot:xxxxxx
Temperatura:xx.xºC
41
In Italian
Description
PV inverter is totally shutdown,
BUS voltage < 200V
IPV <200V & 600V< BUS
IN ATTESA
voltage
Input voltage range 260~350V
during start-up.
When PV voltage> 350V,
VERIFICA RETE xxxs
inverter is checking feeding
conditions
Inverter is feeding power. After
NORMALE
10 seconds of this display, LED
will show wattage.
RICONNESSIONE xxxs The time for reconnect to grid
See "System Fault",
SISTEMA IN ERRORE
"Inverter Fault" to know
the fault detail
Pcc:xxxx/xxxx/xxxxW
The individual DC input power
The real time output power in
Pca:xxxxxW
xxxx W
Total energy to has been fed to
Etot:xxxxxxxxx.xkWh
grid since inverter was installed
Grid voltage in xxx.x VAC for
Vca:xxx.x/xxx.x/xxx.xV
3 phases
Frequenza:xx.x Hz
Grid frequency in xx.x Hz
Feeding current amount in xx.x
Ica:xx.x/xx.x/xx.xA
A
Input voltage of PV array, xxx
Vcc:xxx/xxx/xxxV
VDC
Icc:xx.x/xx.x/xx.xA
Input DC current of tracker
The accumulated kWh of that
Egiorno:xxx.xkWh
day
Ore tot:xxxxxx
Total working hours of inverter
Temperature is indicated in
Temperatura:xx.x°C
Celsius