Grid connect photovoltaic inverter
Hide thumbs Also See for KP100G:
Table of Contents

Advertisement

KP100G
(2) Unscrew the cable gland and prepare AC and Ground(GND) cable. Remove the rubber bushing from inside the AC connector socket.
(3) Insert the provided rubber bushing into the AC connector socket.
Two types of rubber bushing for AC connection as illustrated in Fig, 5-3.
The rubber bushing with 4 holes is used for connection with 4 individual cables.
The rubber bushing with 1 hole is used for connection with multiple-cable.
Rubber sealing for GND cable is already inserted inside of connector.
Now insert the four wires of the AC cable and one wire of GND cable into the bushing holes.
Please note that cross-sectional area of 4 mm
allowed for GND.
(4) Fix 4 wire to L1 (R), L2 (S), L3 (T), and N (Neutral), and a wire to G (Ground).
Rubber bushing (no hole)
Fig, 5-19 Remove the rubber plug
2
is allowed size for AC wires; L1, L2, L3, N, and that a cross-sectional area of 10 mm
Rubber sealing for GND
connector
2 types rubber bushings for
AC connector
Fig, 5-20 Insert the rubber bushing with holes
Fig, 5-21 Connect the AC wire
23
2
or AWG8 is