3.7 Wall Enclosure Rough Opening

IMPORTANT: If this fireplace is installed on an exterior wall, it must be
insulated the same as any other exterior wall to prevent cold air from
entering the home.
IMPORTANT: Allow a minimum of 6" (152mm) in framing
width dimensions for the combustion air duct pipe, which will
be installed after fireplace has been inserted into framing.
See Figure 3.5 on page 14.
CAUTION: Consider the height of the hearth extension when framing
the opening. The height of a hearth extension material may require the
fireplace to be raised on a platform so the hearth extension material
does not block the air inlet and outlet grills. If the air inlet or outlet grills
are blocked, this may cause the fireplace to overheat.
Frame the opening to fit fireplace. All required clearances must
be maintained.
If masonry (optional) is to be used, prepare the foundation
necessary to support the full masonry load. A lintel is required to
support the added weight of the masonry construction above
the fireplace.
(1302mm)
Figure 3.6, Framing Dimensions
#ABY R.2 October 2020
¼
51
"
54"
(1372mm)
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
3.7.1 Steel Framing Assembly
Non-combustible framing is REQUIRED above the fireplace. The steel
studs shown below are included with the fireplace. For installation
and assembly, refer to section 3.5 Steel Framing Assembly Installation
on page 13.
3.7.2 TV Mounting Considerations
Mounting a television above a fireplace is a common practice. Mantel
depth, ceiling heights, and wall and mantel construction material all
affect television surface temperatures. Most television manufacturers
specify in their instructions that a television should not be installed
on, near, or above a heat source.
Television location rests solely on the homeowner. It is the home
owner's responsibility that the preferred TV mounting and mantel
design will not exceed the listed maximum operation temperature of
their electronic goods.
81"
(2.06m)
¼
26
"
(667mm)
Nominal 2" x 4" framing used
INSTALLATION PLANNING 15