Section 3: Hoisting Considerations - CommScope FD21206-48SRC Series Installation Manuallines

Table of Contents

Advertisement

Technical Publication

Section 3: Hoisting Considerations

In general this cable will handle similarly to coaxial cable, and similar installation techniques apply. All cables
are individually serialized, be sure to write down the cable serial number for future reference.
Be sure that the Pendant is not damaged by attachment of a hoisting grip or during the hoisting process.
During hoisting ensure that there is a free path and that the cable.
Installation temperature range is -30 °C to +70 °C (-22 °F to +158 °F).
Maximum cable tensile load can be found on-line in our eCatalog section at www.commscope.com.
CommScope Lace-Up Hoisting Grip 29961-C for FD21206 and FD21204 installation.
Hoisting Grip should be anchored to the support structure after the hangers are installed.
Hybrid Fiber Cables weigh more than traditional coaxial cables. Be sure to follow proper hoisting and
!
attachment procedures.
Keep protected
during hoisting.
Keep 304 mm (1 ft)
of cable below the
Pendant straight during
hoisting and routing.
www.commscope.com
Use a Tie back rope at the base of the
Pendant to secure to the hoisting line
* Be sure that the weight is on the
hoisting grip(s) and not the Pendant
Bulletin # 7843672
Rev. B