Installation
February 2020
Shorten the coaxial probe
Prerequisites
Figure 3-11: Maximum Shortening of Coaxial Probe
A. Ordered probe length (L) > 49 in. (1250 mm)
B. Ordered probe length (L) ≤ 49 in. (1250 mm)
C. Maximum shortening length: 23.6 in. (600 mm)
D. Minimum probe length: 15.7 in. (400 mm)
Procedure
1. Mark where to cut the probe.
38
Pipes longer than 49 in. (1250 mm) can be shortened by as much as 23.6 in.
(600 mm).
Pipes shorter than 49 in. (1250 mm) can be cut as long as the remaining length
is not less than 15.7 in. (400 mm).
Reference Manual
00809-0100-4308
Rosemount 3308 Series