Command and data value descriptions
7.3.26 D_IMD_ERROR_CODE
This data value represents the IMC and VIFC error codes in the error frame.
IMC error codes
Value
Description
32
Timeout 10 ms (incomplete frame)
33
Checksum error detected in frame
34
Invalid parameter
35
Unknown command
36
Error in EEPROM access
37
Repeated or missing frame
VIFC error codes
Value
Description
1000
Command locked
1001
Queue full (Command rejected)
1002
Command unavailable (Measurement Off )
1032
Timeout 10 ms (incomplete frame)
1033
Checksum error detected in data frame
1034
Invalid parameter
1035
Unknown command
1037
Repeated or missing data frame
1038
No response (Timeout 60 ms)
1039
Communication error
1040
Invalid IMC response command
25
Command and data value descriptions
7.3.27 D_IMD_FAILED_CMD
This data value represents the frame command identification of a failed IMC command.
Value
Description
0 ... 255
Every CMD sent in a request to the IMD
iso165C_D00154_03_M_XXEN/01.2019
Need help?
Do you have a question about the ISOMETER iso165C and is the answer not in the manual?
Questions and answers