start cooling (accessory
required)
Setting range: -20 – 40 °C
Factory setting: 25
stop heating
Setting range: -20 – 40 °C
Default values: 17
stop additional heat
Setting range: -25 – 40 °C
Factory setting: 17
filtering time
Setting range: 0 – 48 h
Default value: 24 h
When the operating mode is set to "auto", the electric boiler/indoor module
selects when start and stop of additional heat and heat production are permitted,
depending on the average outdoor temperature. If accessories for cooling are
present or if the heat pump has the integrated cooling function and it is activated
in the menu, you can also select the start temperature for cooling.
Select the average outdoor temperatures in this menu.
filtering time: You can also set the time (filtering time) over which the average
temperature is calculated. If you select 0, the current outdoor temperature is
used.
DEGREE MINUTE SETTING
Menu
4.9.3
72
Chapter 3 | VVM 225 – at your service
Caution
It cannot be set "stop additional heat" higher than "stop heating".
auto mode setting4.9.2
start cooling
stop heating
stop additional heat
filtering time
°C
°C
°C
hrs