FCN 7 - Motion ANDing of Output Channels
(Master Program Enable Input MUST be energized)
This function selects which output channels will be ANDed
with the Motion setpoints as programmed in FCN 1. ANDed
outputs will be on during their programmed pulses only if the
RPM is within the Motion setpoints. In order for Motion
ANDing to take affect, "On" and "Off" pulses must be
programmed into the selected channel.
An output channel can be turned into a motion detector by
programming it to be "On" at 1, "Off" at 1, and then ANDing
it with the Motion setpoints. Setting both points at 1 will turn
the output on for a full 360°. By ANDing this output to the
Motion setpoints, the output will be on constantly as long as
the RPM is within the Motion setpoint range.
on - Output is disabled IF present RPM is not within Motion
setpoints.
oFF - Output will cycle on and off at programmed position
setpoints regardless of present RPM.
Note: Once programmed in a channel, this function will be present in that channel in all programs.
4-8 Programming, Standard Features
1st
If FCN 7
Present output
not shown press:
channel
selected
FCN
7
ENT
2nd
3rd
Press CHN key
to select output #
Present Motion ANDing
status shown for output
selected
Press PULSE key to select
between on and oFF