Master Level Programming, Standard Controls: FCN 0 (continued)
dd - Display Default (PS-51XX after 5/12/92)
Auto, Spd, or PoS can be selected for the display default by
pressing the Pulse key while "dd" is displayed in function 0.
Auto - (Automatic) Display will automatically switch between
POS and RPM when speed goes above and below the "tr"
(toggle RPM) value programmed.
Spd - (Speed) On power up, the control will default to
displaying RPM. The POS/RPM key can be used to switch
between position and RPM display.
PoS - (Position) On power up, the control will default to
displaying position. The POS/RPM key can be used to
switch between position and RPM display.
tr - Toggle RPM (All units after 5/12/92)
When the "Auto" mode is selected as the "dd" (display
default), the value programmed in "tr" determines the speed
where the display switches from position to RPM.
At speeds below "tr", position will be displayed and the
"POS" LED will be lit.
At speed equal to or above "tr", RPM will be displayed and
the "RPM" LED will be lit.
tb - Time Base Used for Output Timing
The timing resolution is selectable between 1 mSec and .5
mSec increments on 8, 9, and 16 output controls (24 and 48
output controls have a fixed 1 mSec tb and do not display
tb in FCN 0). All timed outputs use the same time base.
Timing accuracy of all timed outputs is -0, +1 tb increment.
The number of outputs that can be timed is affected by the
time base selected: (24 and 48 output systems can time up
to 4 outputs)
1mSec tb - Up to 8 outputs can be timed (.001 - 9.999 Sec)
.5 mSec tb - Up to 4 outputs can be timed (.0005 - .9995
Sec)
Note: Adding too many timed outputs will cause an E9
programming error. The ".5" tb value will flash and cannot
be selected if more than 4 timed outputs already exist in

FCN 5.

Consult factory if more timed outputs are required.

Enhanced Position/RPM Display Logic

All PS-51XX (Resolver) Series controls made after 5/12/92
include a feature that allows the user to program the display
default to RPM, position, or automatically switch between
RPM and position. Previous controls always defaulted to
displaying RPM with the POS/RPM key, allowing manual
selection of the item displayed. The POS/RPM key still
4-5 Programming, Standard Features
1st
If FCN 0
dd
not shown press:
display default
selected
FCN
0
ENT
2nd
3rd
Press CHN key
until dd is shown
1st
If FCN 0
tr
not shown press:
toggle rPM
selected
FCN
0
ENT
2nd
Press CHN key
3rd
until tr is shown
1st
If FCN 0
tb
not shown press:
time base
FCN
0
ENT
2nd
3rd
Press CHN key
until tb is shown
allows manual selection of the item displayed on the PS-
5000 versions with the new display logic.
To control these display features, two items have been
added to FCN 0 programming : dd (display default) and tr
(toggle RPM).
Present display
default (dd) shown
Press PULSE key to select
Auto, Spd, or Pos
Present toggle RPM
value shown
Press number keys followed by
ENT to change toggle RPM
Present Time Base
value shown
Press PULSE key to select
1 or .5 mSec Time Base (.5 will
flash if more than 4 timed outputs
exist in FCN 5)