Electro Cam PLUS PS-5000 Series Programming & Installation Manual page 15

Programmable limit switch
Table of Contents

Advertisement

External 16 Module I/O Racks: Dimensions & Specifications
Standard 16 Rack: PS-4100-11-216
Slimline M16 Rack
DIN Rail Rack: PS-4100-11-M16-D
End View
DIN Rail (-D)
Notes:
• A Slimline module is required for each Input or Output used.
See Appendix for module specs.
• AC and DC modules can be mixed as needed.
• Input modules can be used only with 5004 and 5104 units.
• Output modules act like switches; they do not supply
power to loads.
• Analog modules may be installed in position 16 only.
• Module Fuses: 4 Amp, #PS-9005-0004
(Wickman 19370-K)
• "A" Terminals:
"B" Terminals: (+) or hot
3-2 Wiring
End View
Notes:
• A Standard module is required for each Input or
Output used. See Appendix for module specs.
• AC and DC modules can be mixed as needed.
• Input modules can be used only with 5004 and 5104
units.
• Output modules act like switches; they do not
supply power to loads.
• Position 16 of Analog racks is dedicated to analog
output and will not work with other modules. If an
analog module is used, it must be installed in
position 16.
• Odd Terminals: (+) or hot
Even Terminals: (-) or load
(-) or load
PS-5001
PS-5101
PS-5004
PS-5104

Hide quick links: