Malfunction
Flow of water too
fast.
Very low flow of
water.
Outlet temperature
either too hot or all
cold when turned
fully on.
Shower control
cannot be shut off.
Blend temperature
unstable.

2. Cleaning

Many household cleaners contain abrasives and chemical substances, and should not
be used for cleaning plated or plastic fittings. These finishes should be cleaned with
20
Cause
Flow regulators fitted
incorrectly or not
fitted.
Flow regulators fitted
when not required.
Isolating valves not
fully open.
Airlock or partially
blocked pipework.
Blocked shower head.
Hot and cold supplies
have been connected
in reverse.
Pipework not flushed
before connecting the
shower control.
Spray plate in shower
head blocked.
Flow regulators fitted
incorrectly.
Isolating valve partially
closed.
Remedy
Refer to installation
selection chart and check
shower control.
Refer to installation
selection chart and check
shower control.
Open isolating valves.
Flush system and if
appropriate fit float type
automatic air vent.
Remove and clean.
Check connections and
if necessary remove shower
control and turn over and
change outlet fitting and
blanking plug.
Clean shower control and if
if necessary fit new seals.
Refer to the section Spare
Parts.
Descale.
Refer to installation selection
chart and check shower
control.
Open fully.