Heating Circuits Parameters Setting (Direct Circuit, Mixed Circuit 1, Mixed Circuit 2) (For Technician) - Immergas VICTRIX PRO 35 1 I Instructions And Warning Book For The Users

Cascade and zone regulator zone manager
Hide thumbs Also See for VICTRIX PRO 35 1 I:
Table of Contents

Advertisement

Heating circuits parameters setting (direct circuit, mixed circuit 1, mixed circuit 2) (for technician).

This level includes the parameters required for programming
unmixed circ.
the reduced heating mode and the adaptation to the corre-
sponding heating system.
Hc
Entry:
Reduced heating mode.
ReD. heating
setting range:
factory preset:
ECO
Hc
During the reduced operation the following modes can be selected:
ECO:
next parameter
RED:
ECO, RED
ECO
At outside temperatures above the set anti-freeze temperature, the heating
circuit pump is switched-off completely.
At temperatures below frost protection the heating circuit is controlled
with reduced heating characteristics according to the required reduced
temperature (see page 4).
During the reduced mode the heating circuit pump remains activated. The
temperature does not drop below the set minimum temperature value.
Entry: see page 12-13.
Exit without
modifications:via button
Application:
objects with high insulation values.
Application:
objects with low insulation values
Page 24
or automatically after 60 sec.