Domestic hot water parameters setting.

This level includes the necessary parameters for program-
dhw.
ming the hot water economic temperature and the legionella
protection.
Dhw
Entry:
Hot water economic temperature.
Setting range: 10.0 °C up to the required hot water temperature.
dhw
Factory preset: 40 °C.
°C
40.0
Night
This parameter specifies the value of the reduced hot water
temperature outside P1 operating cycle times as well in the
next parameter
operational mode ABSENT for the duration of absence.
Legionella protection (day).
LEGION. prot.
Setting range: OFF, MO SU, ALL
OFF
Factory preset: OFF
day
The legionella protection serves to avoid a legionella infestation
inside the hot water cylinder and is activated on the selected
weekday or on every day. If the hot water temperature is below
65 °C, the cylinder is heated. With the regulation OFF this
function is not effective.
Entry:
see page 12-13.
Exit without
modifications: via button
Application:
supporting temperature inside the cylinder in
order to avoid a cooling down of the tank.
Important:
Other legionella protection times can be regula-
ted exclusively by the heating system specialist.
or automatically after 60 sec.