Parameters Configuration; Setting Of System Parameters (For The Technician) - Immergas VICTRIX PRO 35 1 I Instructions And Warning Book For The Users

Cascade and zone regulator zone manager
Hide thumbs Also See for VICTRIX PRO 35 1 I:
Table of Contents

Advertisement

PARAMETERS CONFIGURATION.

Setting of system parameters (for the technician).

SySTEM
This level includes general delimiting parameters and options referring
to the corresponding heating system.
SyST.
Entry:
Language choice
setting range:
Language
factory preset: I
SyST.
I
All information appearing on the display are available in the languages Ita-
lian, German, English and French. After entry as first parameter appears the
next parameter
language selection. The required language can be selected according to the
above assignment.
Operating times program
setting range: P1, P1-P3
PROGRAM
standard: P1
P1
SyST.
This parameter specifies the number of the cleared time programs. With the
next parameter
regulation P1 only one operating times program is available. With the setting
value P1-P3 all three programs are cleared and taken into consideration for
programming operating times.
I = ITALIAN
GB = ENGLISH
F = FRENCH
D = GERMAN
Entry:
See "Programming of functioning
parameters" page 12-13.
Exit:
Button
or automatically after 60
seconds
Modify:
Confirm selected flashing parameter
by pressing the knob. Then set the new
required value via the knob and accept
by pressing the knob again.