7 . W i r e l e s s F u n c t i o n s

7.1 Site Options

In 'SITE OPTIONS' function there are 3 functions
for the Enforcer 32-WE:
Set With Polling Fault: This allows the Enforcer
32-WE to set even if a device has missed 20
minutes worth of device polls.
[0] No [1] Yes
Fob Unset Entry: If this function is enabled a
keyfob can only be used to unset the control panel
when the entry time is counting down.
[0] No [1] Yes
Wireless Bell Supervision: If this function is
enabled, the bell performs its own supervision and
jamming protection, and will alarm if either
condition occurs (this cannot be silenced by the
panel). The alarm will stop after the bell expiry
time, when the jamming stops or when a
supervision message has been received by the
panel. If this function is disabled, it will work the
same way as an input. No supervision or jamming
will be detected by the bell, but the Enforcer 32-
WE will still detect both depending on the timers.
[0] No [1] Yes

7.2 Change Timers

In 'CHANGE TIMERS' there are 2 functions for the
wireless operation:
Wireless Supervision Time: This is the time
window before a supervision fault will be signalled.
For example: if the time is set for 2 hours, then
any device that doesn't communicate with the
Enforcer 32-WE within that period will cause a
supervision fault.
[0-99] hours (0=supervision faults ignored)
NOTE: Must be set to 2 hours or less to comply
with EN50131.
Wireless Jamming Time: This is the time window
that monitors the signals of each wireless device. If
a signal is 'blocked' for longer that the
programmed time a fault will be displayed. [0-100]
seconds (0=jamming faults ignored). NOTE: It is
not recommended to program less than 10
seconds. Must be set to 30 seconds or less (but not
to zero) to comply with EN50131.
Enforcer 32-WE Wireless Setup Manual
Page: 12
In the Engineer Menu
Use  and to scroll to:
SITE OPTIONS?
Press 
Set with Poll FL
No
Use [ or ]. Press 
Fob Unset Entry
No
Use [ or ]. Press 
Wirls Bell Sprv
No
Press 
In the Engineer Menu
Use  and to scroll to:
CHANGE TIMERS?
Press 
Wirls Sprvn Time
Enter Value. Press 
Wirls Jmmng Time
Enter Value. Press 
[0]
[0]
[0]
[02]
[030]