Examples of installation (damper blade outside fire separating construction) -
EIS 90
Installation outside of solid wall
5
4
3
Installation outside of
solid ceiling construction
2
1
Fire damper FDMB
2
Mortar or gypsum with min. density 800 kg/m
or another approved fire sealing system for
damper installation
3
Stuffing box (mineral stone wool min. density
140 kg/m ) or another approved fire sealing
3
system for damper installation
4
Fire protection mastic Promastop P,K or equal
min. thickness 1 mm
Other installation systems including installations with using of installation frames are available in
TPM 075/09 or at www.mandik.com.
Square fire dampers
construction
5
4
3
3
6
7 8
1
Installation outside of gypsum
6
8
7
1
5
Cement lime plate Promatect-H or equal min.
thickness 15 mm (min. density 870 kg/m )
6
Stone wool bound with use of an organic resin
with crushed stone as a refrigerant (min. density
300 kg/m ), EIS 90, thickness 60 mm or another
3
approved fire insulation system
7
VRM-III
8
Profil U25x40x25
15
022/12 BE
wall construction
6
7 8
3
1