Examples of installation (damper blade outside fire separating construction) -
Installation outside of solid wall
EIS 90
5
4
3
Installation outside of
solid ceiling construction
2
1
Fire damper FDMB
2
Mortar or gypsum with min. density 800 kg/m
or another approved fire sealing system for
damper installation
3
Stuffing box (mineral stone wool min. density
140 kg/m ) or another approved fire sealing
3
system for damper installation
4
Fire protection mastic Promastop P,K or equal
min. thickness 1 mm
Round fire dampers
construction
7
5
4
6
3
6
Installation outside of gypsum
3
7
1
5
Cement lime plate Promatect-H or equal min.
thickness 15 mm (min. density 870 kg/m )
6
Stone wool with one side stitched wire fencing
(min. density 105 kg/m ), thickness 180 mm or
another approved fire insulation system
7
Stone wool with one side stitched wire fencing
(min. density 105 kg/m ), thickness 60 mm or
another approved fire insulation system
13
022/12 BE
1
wall construction
7
3
3
6
1
3