Mandik FDMB Installation Instructions Manual page 12

Hide thumbs Also See for FDMB:

Advertisement

Installation in a solid ceiling construction
EIS 120
EIS 90
1
Fire damper FDMB
2
Mortar or gypsum with min. density 800 kg/m
or another approved fire sealing system for
damper installation
Installation in a solid ceiling construction
EIS 90
1
Fire damper FDMB
2
Stuffing box (mineral stone wool min. density
140 kg/m ) or another approved fire sealing
3
system for damper installation
3
Fire protection mastic Promastop P,K or
equal min. thickness 1 mm
4
Cement lime plate Promatect-H or equal min.
thickness 15 mm (min. density 870 kg/m )
Installation in a solid ceiling construction (Weichschott system)
EIS 90
1
Fire damper FDMB
2
Fire resistant board
3
Fire stop coating thickness 1 mm
Used materials - example:
2 - Hilti CP673 PF
3 - Hilti CP673
Notice:
- Solid wall construction: normal concrete/masonry or porous concrete with minimum thickness 100 mm
- Solid ceiling construction: normal concrete/masonry or porous concrete with minimum thickness 150 mm
3
3
11
2
2
3
4
3 2
022/12 BE
1
Min. 50
1