7 SPECIFICATIONS

7.1 Inverter rating
00023
Model FR-F846-ã
(0.75K)
*1
0.75
Applicable motor capacity [kW]
*2
1.6
Rated capacity [kVA]
Rated current [A]
2.1
*3
120% of rated motor capacity for 60 s, 150% of rated motor capacity for 3 s (max. surrounding air temperature 40 °C)
Overload current rating
*4
Three-phase 380 to 500 V
Rated voltage
Rated input AC voltage/
Three-phase 380 to 500 V 50 Hz/60 Hz
frequency
Permissible AC voltage
323 to 550 V 50 Hz/60 Hz
fluctuation
Permissible frequency
±5%
fluctuation
*5
2.1
Rated input current [A]
Power supply capacity
1.6
*6
[kVA]
Dust- and water-proof type (IP55)
Protective structure
UL Type12
Cooling system
Self-cooling + internal fan
DC reactor
Built-in
Approx. mass [kg]
15
*1
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi Electric 4-pole standard motor.
*2
The rated output capacity indicated assumes that the output voltage is 440 V.
*3
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for the
inverter and motor to return to or below the temperatures under 100% load.
*4
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However, the
maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about √2.
*5
The rated input current indicates a value at a rated output voltage. The impedance at the power supply side (including those of the input reactor and cables) affects
the rated input current.
*6
The power supply capacity is the value when at the rated output current. It varies by the impedance at the power supply side (including those of the input reactor
and cables).
*7
For the power voltage exceeding 480 V, set Pr. 977 "Input voltage mode selection". (For details, refer to the FR-F800 Instruction Manual (Detailed).)
*8
UL Type 12 Enclosure-Suitable for Installation in a Compartment Handling Conditioned Air (Plenum)
*9
For compliance with IP55, remove the protective bushes and install the recommended cable glands.
00038
00052
00083
00126
00170
(1.5K)
(2.2K)
(3.7K)
(5.5K)
(7.5K)
1.5
2.2
3.7
5.5
7.5
11
2.7
3.7
5.8
8.8
12
3.5
4.8
7.6
11.5
16
23
*7
3.5
4.8
7.6
11.5
16
2.7
3.7
5.8
9
12
*9
*8
Forced-air-cooling + internal fan
15
15
15
16
17
26
00250
00310
00380
00470
00620
(11K)
(15K)
(18.5K)
(22K)
(30K)
15
18.5
22
30
37
18
22
27
33
43
53
29
35
43
57
70
23
29
35
43
57
70
18
22
27
33
43
53
26
27
27
59
60
00770
00930
01160
01800
02160
02600
(37K)
(45K)
(55K)
(75K)
(90K)
(110K)
45
55
75
90
110
65
81
110
137
165
85
106
144
180
216
85
106
144
180
216
65
81
110
137
165
63
64
147
150
153
03250
03610
(132K)
(160K)
132
160
198
248
260
325
260
325
198
248
189
193
35

Advertisement

loading