BASIC OPERATION
5.2 Parameter list
For simple variable-speed operation of the inverter, the initial values of the parameters may be used as they are. Set the necessary
parameters to meet the load and operational specifications. Parameter setting, change and check can be performed from the
operation panel (FR-LU08-01).
Remarks
l
Simple
Simple
Simple
indicates simple mode parameters. Use Pr. 160 "User group read selection" to indicate the simple mode parameters
only.
l The changing of the parameter settings may be restricted in some operating statuses. Use Pr. 77 "Parameter write selection"
to change the setting of the restriction.
l Refer to the FR-F800 Instruction Manual (Detailed) for instruction codes for communication and availability of Parameter
clear, all clear, and Parameter copy.
Parameter Name
0
Simple
Simple
Simple
Torque boost
Maximum frequency
1
Simple
Simple
Simple
Minimum frequency
2
Simple
Simple
Simple
Base frequency
3
Simple
Simple
Simple
Multi-speed setting
4
Simple
Simple
Simple
(high speed)
Multi-speed setting
(middle speed)
5
Simple
Simple
Simple
Multi-speed setting
6
Simple
Simple
Simple
(low speed)
Acceleration time
7
Simple
Simple
Simple
Deceleration time
8
Simple
Simple
Simple
Electronic thermal
Simple
Simple
Simple
O/L relay
9
Rated motor current
Simple
Simple
Simple
DC injection brake
10
operation frequency
DC injection brake
11
operation time
DC injection brake
12
operation voltage
13
Starting frequency
14
Load pattern selection
15
Jog frequency
Jog acceleration/
16
deceleration time
*1
Differs according to capacities.
l 6%: FR-F846-00023(0.75K)
l 4%: FR-F846-00038(1.5K) to 00083(3.7K)
l 3%: FR-F846-00126(5.5K) and 00170(7.5K)
l 2%: FR-F846-00250(11K) to 00770(37K)
l 1.5%: FR-F846-00930(45K) and 01160(55K)
l 1%: FR-F846-01800(75K) or higher
*2
For FR-F846-01160(55K) or lower
*3
For FR-F846-01800(75K) or higher
*4
For FR-F846-00170(7.5K) or lower
*5
For FR-F846-00250(11K) or higher
*6
Differs according to capacities.
l 4%: FR-F846-00170(7.5K) or lower
l 2%: FR-F846-00250(11K) to 01160(55K)
l 1%: FR-F846-01800(75K) or higher
20
Setting Range
Initial Value
6/4/3/2/1.5/
0 to 30%
*1
1%
*2
120 Hz
0 to 120 Hz
*3
60 Hz
0 to 120 Hz
0 Hz
50 Hz
0 to 590 Hz
50 Hz
0 to 590 Hz
30 Hz
0 to 590 Hz
10 Hz
0 to 590 Hz
*4
5 s
0 to 3600 s
*5
15 s
*4
10 s
0 to 3600 s
*5
30 s
*2
0 to 500 A
Inverter
rated
current
*3
0 to 3600 A
0 to 120 Hz, 9999
3 Hz
0.5 s
0 to 10 s, 8888
*6
0 to 30%
4/2/1%
0 to 60 Hz
0.5 Hz
1
0, 1, 12 to 15
5 Hz
0 to 590 Hz
0.5 s
0 to 3600 s
Parameter Name
17
MRS input selection
High speed maximum
18
frequency
Base frequency
19
voltage
Acceleration/
20
deceleration reference
frequency
Acceleration/
21
deceleration time
increments
Stall prevention
22
operation level
Stall prevention
operation level
23
compensation factor
at double speed
Multi-speed setting
24 to 27
(4 speed to 7 speed)
Multi-speed input
28
compensation
selection
Acceleration/
29
deceleration pattern
selection
Regenerative function
30
selection
31
Frequency jump 1A
32
Frequency jump 1B
33
Frequency jump 2A
34
Frequency jump 2B
35
Frequency jump 3A
36
Frequency jump 3B
37
Speed display
Up-to-frequency
41
sensitivity
Output frequency
42
detection
Setting Range
Initial Value
0
0, 2, 4
*2
120 Hz
0 to 590 Hz
*3
60 Hz
0 to 1000 V, 8888,
8888
9999
50 Hz
1 to 590 Hz
0
0, 1
110%
0 to 400%
9999
0 to 200%, 9999
9999
0 to 590 Hz, 9999
0
0, 1
0
0 to 3, 6
0, 2, 10, 20, 100,
0
102, 110, 120
9999
0 to 590 Hz, 9999
9999
0 to 590 Hz, 9999
9999
0 to 590 Hz, 9999
0 to 590 Hz, 9999
9999
9999
0 to 590 Hz, 9999
0 to 590 Hz, 9999
9999
0
0, 1 to 9998
10%
0 to 100%
6 Hz
0 to 590 Hz