WIRING
2.2 Main circuit terminal
2.2.1 Terminal layout and wiring
FR-F846-00023(0.75K) to FR-F846-00170(7.5K)
Charge lamp
Power supply
R/L1 S/L2 T/L3
Power supply
FR-F846-00620(30K) to FR-F846-01160(55K)
Charge lamp
R/L1 S/L2 T/L3 N/-
Power supply
CAUTION
l The power supply cables must be connected to R/L1, S/L2, T/L3. Never connect the power cable to the U, V, W, of the inverter.
Doing so will damage the inverter. (Phase sequence needs not to be matched.)
l Connect the motor to U, V, W. At this time turning on the forward rotation switch (signal) rotates the motor in the clockwise
direction when viewed from the motor shaft. (The phase sequence must be matched.)
6
Jumper
N/-
P/+
Motor
M
Motor
Jumper
P/+
M
Motor
FR-F846-00250(11K) to FR-F846-00470(22K)
Charge lamp
R/L1 S/L2 T/L3 N/-
Power supply
FR-F846-01800(75K) to FR-F846-03610(160K)
Charge lamp
R/L1 S/L2 T/L3
N/-
Power supply
Jumper
P/+
M
Motor
P/+
M
Motor
Jumper