Mitsubishi Electric 800 Series Installation Manualline page 9

Inverter for fans and pumps
Hide thumbs Also See for 800 Series:

Advertisement

1.3 Environment
Before installation, check that the environment meets following specifications:
Ambient temperature
Ambient humidity
Storage temperature
Atmosphere
Altitude
Vibration
*1
Temperature applicable for a short time, e.g. in transit.
*2
For the installation at an altitude above 1,000 m, derate the rated current 3% per 500 m.
*3
2.9 m/s² or less for the FR-F846-01160(55K) or higher
1.4 Installing a communication option (FR-F846-E)
To use a communication option, the enclosed earthing (grounding) cable needs to be installed. Install the cable according to the
following procedure:
a Insert spacers into the mounting holes that will not be tightened with the option mounting screws.
b Fit the connector of the communication option to the guide of the connector of the inverter, and insert the option as far as it
goes. (Insert it to the inverter option connector 1.)
c Remove the mounting screw (lower) of the Ethernet board earth plate. Fit the one terminal of the earthing (grounding) cable
on the Ethernet board earth plate and fix it securely to the inverter with the mounting screw (tightening torque 0.33 Nm to
0.40N m).
d Fix the left part of the communication option securely with the option mounting screw, and place another terminal of the
earthing (grounding) cable on the right part of the option and fix the cable terminal and the option with the option mounting
screw (tightening torque 0.33 Nm to 0.40 Nm).
If the screws are not tightened properly, the connector may not be inserted deep enough. Check the connector.
Spacer
Ethernet board
earth plate
Example FR-A8NC
Notes
l The number and shape of the spacers used differ depending on the communication option type. Refer to the Instruction
Manual of each communication option for details.
l The earth plate enclosed with a communication option is not used.
–10 °C to +40 °C (non-freezing)
95 % RH or less (non-condensing)
*1
–20 °C to +65 °C
Indoors (No corrosive and flammable gases, oil mist, dust and dirt)
*2
Maximum 2,500 m
*3
5.9 m/s²
or less at 10 to 55 Hz (directions of X, Y, Z axes)
Option connector 1
Spacer
Earth cable
INSTALLATION AND INSTRUCTIONS
Mounting screw
Ethernet board
earth plate
Enclosure
x = Measurement position
5 cm
5 cm
5 cm
Mounting screw
Spacer
Spacer
Mounting screw
Earth cable