APPENDIX
Branch circuit protection
For installation Class T, Class J, Class CC, or Class L fuse, or UL 489 Molded Case Circuit Breaker (MCCB) according to the local direc-
tives must be provided.
FR-F846-ã
Rated fuse voltage [V]
Fuse allowable rating [A]
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
FR-F846-ã
Rated fuse voltage [V]
Fuse allowable rating [A]
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1
Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
*2
Select an appropriate molded case circuit breaker with a rating that is suitable for the size of the cable.
A.1.3 Short circuit ratings
l 400 V class
Suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 500 V maximum.
A.1.4 Machinery directive
The frequency inverter itself is not a machine in the spirit of the EU machinery directive. The start up of the frequency inverter in a
machine is prohibited so long until it has been confirmed that the entire machine complies with the provisions of Directive 98/37/
EC (from 29.12.2009 Machinery Directive 2006/42/EC).
40
00023
00038
00052
(0.75K)
(1.5K)
(2.2K)
6
10
15
15
*1
00620
00770
00930
(30K)
(37K)
(45K)
125
150
150
175
*1 *2
00083
00126
00170
(3.7K)
(5.5K)
(7.5K)
500 V or more
10
15
25
15
20
30
01160
01800
02160
(55K)
(75K)
(90K)
500 V or more
175
200
250
225
250
450
00250
00310
00380
(11K)
(15K)
(18.5K)
35
60
70
40
60
70
02600
03250
03610
(110K)
(132K)
(160K)
300
350
400
450
500
—
00470
(22K)
90
100
90
100
500
—