User Interface; Display And Buttons - ETC Echo Integration Interface Installation Manual

Table of Contents

Advertisement

ETC Installation Guide
Integration Interface
24 VDC
24 VDC is required to power the interface. Two terminals are
provided and accept 16 AWG (1.5 mm
1.
2.
3.
4.
Ethernet
An RJ45 receptacle provided for Ethernet connection is located on the
bottom of the interface. This connection complies with the EIA/TIA
standard. Connect to the Integration Network.
Note:
network.
Power Up
Once the Integration Interface is connected to the EchoConnect station
bus and power is applied, the power LED will indicate steady blue and the
display will power on.

User Interface

Display and Buttons

On initial power up, the display will show Integration Interface (which is
the device name), its default IP address (10.101.19.201), its UDP Receive
Port number, and Subscriber security setting.
The display automatically sleeps after two minutes of inactivity and wakes
again with any button press.
Navigation Buttons
Buttons are provided to navigate the Integration Interface menu and edit
selected fields.
Integration Interface
Strip 5/16" (8 mm) of insulation from the bare end
of each wire.
Loosen the two screw terminals on the 24 VDC terminals.
Insert the negative (or common) wire (black wire typical) into the
negative (-) terminal and tighten the screw firmly onto the wire.
Insert the positive (+) wire (red wire typical) into the positive (+)
terminal and tighten the screw firmly onto the wire.
The Integration Network may differ from any ETC lighting
(up) and
(down) navigate the menu, or when a parameter
selection is made, press (or press and hold) to increase / decrease
the value
(back) navigates to the previous menu selection
(enter) commits a selection or edit
2
) wires.
Page 4 of 8