The product meets the technical requirements of EN/IEC 61000-3-3.
Decide the length and size of the power supply cable based on the maximum ampere tabulated above in accordance with the national wiring regulations.
Select the fuse(s) and/or circuit breaker(s) from the types and ratings suitable for the maximum ampere tabulated above in accordance with the national wiring
regulations.
If capacity of power supply circuit and enforcement are not enough, it can causes the electric shock and a fire.
(1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units except any one of the
outdoor units. (When shipping: In shorted condition.)
For a system without link (no wiring connection between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop.
Outdoor unit
Indoor unit
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-address setting.
Outdoor unit
NO
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
Central Controller
(5) Use shielded wires for inter-unit control wiring and ground the shield on both sides,
otherwise misoperation from noise may occur. Connect wiring as shown in Section
"
Wiring System Diagrams" on page 1-11-2.
(6) Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conform to CENELEC (HAR) rating specifications) or use the
cables based on IEC standard. (60245 IEC57, 60245 IEC66)
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also occur.
Therefore, ensure that all wiring is tightly connected.
WARNING
When connecting each power wire to the terminal, follow the instructions on "How to connect wiring to the terminal" and fasten the wire
securely with the terminal screw.
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
: Branch point
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
1-11-7
Outdoor unit
Prohibited
Indoor unit
Indoor unit
Indoor unit
Branch point
Indoor unit
Indoor unit
Shielded wire
(Functional earthing)
Prohibited
Indoor unit
Indoor unit
Indoor unit
(Functional earthing)
1