Panasonic Elite Big PAC-i S-200PE3E5B Technical Data & Service Manual page 271

Dc inverter
Hide thumbs Also See for Elite Big PAC-i S-200PE3E5B:
Table of Contents

Advertisement

Sensor Temperature Display Function
(displayed regardless of whether unit
is operating or stopped)
The procedure below display the sensor temperatures
from the remote controller, indoor unit, and outdoor
unit on the remote controller.
<Procedure of CZ-RTC4>
(1)
Press and hold the
simultaneously for 4 seconds or longer.
(2)
The unit No. "X-X" (main unit No.), item code "
(sensor address), and servicing monitor "
(sensor temperature) are displayed on the remote
controller LCD display. (See Fig. 7-10 at right.)
(3)
Press the temperature setting
and select the item code to the address of the
sensor to monitor.
(4)
If group control is in effect, press the
to select the unit to monitor.
Press the temperature setting buttons to select the
item code to change.
(5)
Press the
button to return to normal remote
controller display.
NOTE
The temperature display appears as "- - - -" for units that are not connected.
* If monitor mode is engaged while normal operation is in progress, only the parts of the LCD display shown in
the figure will change. Other parts continue to display the same information as during normal operation.
Item code
Indoor unit data
Outdoor unit data
* Depending on the model, some items may not be displayed.
and
buttons
/
buttons
button
02
Indoor unit intake temp.
03
Indoor unit heat exchanger temp. (E1)
04
Indoor unit heat exchanger temp. (E2)
05
06
07
08
09
0A
Discharge temp. (TD)
0b
0C
0d
Intake temp. (TS)
0E
Outdoor unit heat exchanger temp. (C1)
0F
Outdoor unit heat exchanger temp. (C2)
10
11
Outdoor air temp. ( TO )
12
13
Current value (CTL2)
14
Current value (CTL1)
15
Outdoor MV value (MOV1)
16
19
Frequency
"
"
A
(3)(4)
(5)
Meaning of Code
7-21
°
°
(1)
Fig. 7-10
(3)
(4)
(2)
(4)
7