Panasonic Elite Big PAC-i S-200PE3E5B Technical Data & Service Manual page 265

Dc inverter
Hide thumbs Also See for Elite Big PAC-i S-200PE3E5B:
Table of Contents

Advertisement

(Continued from previous page)
Item code
Heat exchanger
3C
temperature for cold air
discharge
3d
Fan output switching
Drain pump delayed stop
3E
time
45
DC flap operation mode
46
DC flap swing mode
5d
DC fan tap setting
Stop at time set for OFF
5F
timer after operation starts
Timer function change
60
prohibit
62
Smudging control
NOTE
Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.
Do not change any setting data that does not appear in this list.
Item
The heat exchanger temperature control point for prevention of cold
air discharge during heating operation can be changed.
The indoor unit PCB optional output for the fan can be switched
according to the purpose of use.
The drain pump stops after the set time delay after cooling operation
stops.
Changes flap operation to draft reduction mode.
Selects the swing operation mode for the flap.
Sets the DC fan tap according to the purpose of use.
Change the settings data at the same time.
This setting enables a function that stops operation when the
amount of time set for the OFF timer has passed after remote
controller operation was started.
This function prohibits changes from being made to the remote
controller time setting.
Smudging control is disabled when 0000 is set.
Description
7-15