7-6. Detailed Setting Items

Item code
Item
10
Unit type
11
Indoor unit capacity
System (outdoor unit)
12
address
13
Indoor unit address
14
Group address
Cooling intake
17
temperature shift
Automatic stop time after
18
operation start
Forced thermostat ON
1b
time
Temperature shift for
1E
cooling / heating change
in "auto heat / cool" mode
Cooling temperature setting
Cooling temperature setting
Remote controller temperature setting
Remote controller temperature setting
Heating temperature setting
Heating temperature setting
Set when the indoor unit EEPROM memory is replaced during servicing.
These are not set at the time of shipping from the factory.
These must be set after installation if automatic address setting is not
performed.
Shifts the intake temperature during cooling and dry operation.
(Enabled only when the body thermostat is used.)
Increase this value when it is difficult to turn the thermostat ON.
The time at which an indoor unit is automatically stopped after operation
starts can be set in increments of 5 minutes.
Use this setting to change the time for forced operation at installation
or servicing from 5 minutes to 4 minutes.
"Auto heat / cool" selects the operating mode automatically based on
the difference between the room temperature and the temperature set
on the remote controller. This setting establishes a shift temperature for
the heating / cooling temperature setting relative to the remote controller
temperature setting.
Shift temperature
Shift temperature
Shift temperature
Shift temperature
7-13