Front Panel Indicators - Eaton Ferrups FX User Manual

Table of Contents

Advertisement

Front Panel Indicators

Indicator Lights
There are five indicators located on the Remote Control Display and a light bar that indicate the operating mode
of the UPS. The light color will change depending on the mode of the UPS.
Table 13. Indicator Status
Indicator
AC Line
Ready
Charging
On Batt
Alarm
Light Bar
34
Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User's Guide P-164000906—Rev 05
Color
Status
Blue
On
Off
Blue
On
Off
Flashing
Blue
On
Off
Yellow
On
Off
Red
On
Off
Blue, Yellow, Red
On
Explanation
The UPS is getting power from the AC input power
source.
The UPS is not getting input power.
Input could be outside of the acceptable
limits.
There is a power outage.
The AC input breaker is tripped.
The UPS is unplugged.
The UPS is ready to provide backup power when
needed.
The UPS cannot provide battery backup power
because:
The UPS is in the Off mode.
The UPS may be running on battery power
(Inverter Mode).
The UPS is in Line Condition Mode
The UPS is charging the batteries.
The battery charger is off; batteries are at full
charge.
The UPS is providing power from its batteries;
it is in the Inverter On mode.
The UPS is providing conditioned power from the
AC input power source, or the UPS is off.
The UPS is warning you that an alarm exists
No alarm exists.
The light bar will change color depending on the
state of the UPS
Blue : UPS is operating without alarms or
warnings
Yellow: UPS is operating on battery power.
Red: The UPS is indicating an alarm
condition.

Hide quick links: