Summary of Contents for Eaton MX Frame 15000 RT

  • Page 1 MX Frame 15000 RT 20000 RT Installation and user manual Pulsar Series...
  • Page 2: Environmental Protection

    Before installing MX, please read the booklet on the required safety instructions. Then follow the indications in this manual. To discover the entire range of EATON products and the options available for the MX range, we invite you to visit our web site at www.eaton.com or contact your EATON representative.
  • Page 3 Introduction Pictograms Important instructions that must always be followed. Information, advice, help. Visual indication. Action. Audio signal. In the illustrations on the following pages, the symbols below are used: LED off LED on 34008486EN/AC Page 4...
  • Page 4: Table Of Contents

    1.1 Wheels position ..........................8 1.2 Rack position ..........................8 1.3 Sub-modules ..........................8 1.4 Rear panels ............................ 9 MX Frame 15000 RT / 20000 RT ....................9 1.5 Display and control panel ......................10 Sub-module pictograms on display ....................10 1.6 Battery extension .........................11 Battery extensions for MX Frame ....................11...
  • Page 5 Contents 2.7 Connections of input/output power cables ................23 Input connection ..........................23 Access to terminal block .....................23 Single phase input ........................24 Common sources .........................24 Separate sources ........................24 Three phases input ........................25 Common sources .........................25 Separate sources ........................25 2.8 Fix the terminal block cover .......................26 2.9 Extended battery (EXB) connections ..................27 2.10 Connection of IEC cables to output receptacles ..............27 3.
  • Page 6 Contents 6. Life Cycle Monitoring (LCM) 6.1 Description ........................... 38 Get free offers ..........................38 Secure your installation power continuity ................... 38 Reset or disable LCM ........................ 39 7. Maintenance 7.1 Hot swapping the power sub-module ..................40 Disconnecting the power sub-module : ................40 Reconnecting the power sub-module : ................
  • Page 7: Presentation

    1. Presentation Wheels position Dimensions (H x W x D) MX Frame 688x445x738 mm 15 000 RT/ 20 000 RT 27 x 18 x 29 inches (on wheels) Weights MX Frame 71 kg 157 lbs MX Frame 194 kg 15 000 RT 428 lbs MX Frame 239 kg...
  • Page 8: Rear Panels

    1. Presentation Rear panels MX Frame 15000 RT / 20000 RT (1) Normal AC source input switch (2) Single phase or three-phase input selection (3) Residual-current earth-leakage circuit breaker 30mA for PDU1 and PDU2 (4) Groups of 2 (10A) outlets for...
  • Page 9: Display And Control Panel

    (15) Load powered LED Sub-module pictograms on display (1) Sub-modules detection (2) The power sub-module and the battery sub-module are not detected on the level (MX Frame 15000 RT) (3) Internal battery sub-module fault detected (4) Internal power sub-module fault detected For internal sub-module fault description, see section 5.2, page 35...
  • Page 10: Battery Extension

    1. Presentation Battery extension MX Frame offers a standard backup time of 5 minutes at full load. To increase backup time up to 62 minutes (at full load), it is possible to connect MX EXB RT modules to the UPSs. Battery extensions for MX Frame MX EXB RT (optional battery module) (1) Connectors for automatic detection of...
  • Page 11: Installation

    2. Installation Unpacking and contents check Unpacking Keep the packaging parts for wheels removal. Contents check (1) MX FRAME 15 000 RT or 20 000 RT UPS. (7) 4 cable lockers. (2) Solution-Pac power management suite CD-ROM. (8) 8 IEC 10A output cables. (3) Product documentation.
  • Page 12: Rack Mounting

    2. Installation Rack mounting Wheels removal The battery sub-modules and power sub-modules must no be mounted yet. It is not allowed to install the UPS or battery module in a hermetically closed environment without any exchange of air. 1 - Use packaging as shown. 2 - Place MX Frame on its side.
  • Page 13: Ups Module Rack Mounting

    Follow steps 1 to 4 for rack mounting the UPS onto the rails. The rails and the necessary mounting hardware are supplied by EATON. Note for step 1: it is possible to adjust the position of both front mounting ears.
  • Page 14: Mounting Sub-Modules

    2. Installation Mounting sub-modules A dangerous voltage is present inside the power module and the battery module. Any operations to be carried out on these modules must be done by qualified staff. You must mount the modules from the lowest level to the highest level. All the sub-modules must be mounted.
  • Page 15: Communication Ports

    MX RT provides 3 communication methods that can be used simultaneously: 2 COM ports provide RS232 or USB communications using EATON SHUT protocol. Compatible with most power management software applications available into the enclosed Solution Pac CD-Rom. Please, note that both ports cannot be used at the same time.
  • Page 16: Installation Of Communication Card

    2. Installation Installation of communication card It is not necessary to shutdown the UPS before installing a communications card. 1 - Remove the slot cover (1) secured by two screws. 2 - Insert the communication card (2) in the slot. 3 - Secure the card with both screws.
  • Page 17: Required Protective Devices And Cable Cross-Sections

    2. Installation Required protective devices and cable cross-sections Recommended upstream protection The indicated protection ensures UPS power rating Upstream circuit breaker discrimination for each output circuit 15000/20000 RT D curve - 125 A downstream of the UPS. If these recommendations are not followed, protection discrimination is not achieved and may result in a potential power interruption to the connected...
  • Page 18: Installation Depending On The System Earthing Arrangement (Sea)

    2. Installation Installation depending on the system earthing arrangement (SEA) Single phase input UPS with common Normal and Bypass AC inputs Main low- voltage switchboard (MLVS) load Change in SEA between upstream and downstream or galvanic isolation required Main low- voltage switchboard (MLVS)
  • Page 19: Ups With Separate Normal And Bypass Ac Inputs, Supplied By Separate Sources

    2. Installation UPS with separate Normal and Bypass AC inputs, supplied by separate sources MLVS 1 load MLVS 2 MLVS 1 load MLVS 2 Change in SEA between upstream and downstream or galvanic isolation required MLVS 1 load MLVS 2 Frequency converter (without Bypass AC input) Configuration used when the frequency of the application differs from the Mains (Example : marine requirements).
  • Page 20: Three Phases Input

    2. Installation Three phases input MX Frame must be fed from a 3-phase source with neutral. UPS with common Normal and Bypass AC inputs Main low- voltage switchboard (MLVS) load Change in SEA between upstream and downstream or galvanic isolation required Main low- voltage switchboard...
  • Page 21: Ups With Separate Normal And Bypass Ac Inputs, Supplied By Separate Sources

    2. Installation UPS with separate Normal and Bypass AC inputs, supplied by separate sources MLVS 1 load MLVS 2 MLVS 1 load MLVS 2 Change in SEA between upstream and downstream or galvanic isolation required MLVS 1 load MLVS 2 Frequency converter (without Bypass AC input) Configuration used when the frequency of the application differs from the Mains (Example : marine requirements).
  • Page 22: Connections Of Input/Output Power Cables

    2. Installation Connections of input/output power cables This type of connection must be carried out by qualified electrical personnel Before carrying out any connection, check that the upstream protection device Normal AC source is open ("O") (OFF) Input connection Access to terminal block 1 - Remove the 2 screws of the terminal block cover (1).
  • Page 23: Single Phase Input

    2. Installation Single phase input This type of connection must be carried out by qualified electrical personnel Common sources 1 - Be sure that the one-phase metal strap is installed 2 - Be sure that the metal jumper is installed 3 - Connect the 3 cables to the normal AC source terminal block 4 - Connect the 3 cables to the output...
  • Page 24: Three Phases Input

    2. Installation Three phases input This type of connection must be carried out by qualified electrical personnel Common sources 1 - Remove the one-phase metal strap (1) 2 - Be sure that the metal jumper (2) is installed 3 - Connect the 5 cables to the normal AC source terminal block 4 - Connect the 3 cables to the output terminal block...
  • Page 25: Fix The Terminal Block Cover

    2. Installation Fix the terminal block cover This type of connection must be carried out by qualified electrical personnel 1 - Push up the moving tray (1). 2 - Push in the moving tray (1). 3 - Fix the 2 screws of the terminal block cover (2).
  • Page 26: Extended Battery (Exb) Connections

    16 A outlet (4). To program shutdown of outlets (2) during operation on battery power and thus optimise the available backup time, the EATON communication software is required. 2 - Fit the connection securing system (5) that prevents the plugs from being pulled out accidentally.
  • Page 27: Operation

    3. Operation Initial start-up It is essential to contact our Customer Service to ensure that your system is commissionned in complete safety and to benefit from the manufacturer’s guarantee. 1 - Be sure that the manual bypass switch (1) is in normal position, like shown on the picture.
  • Page 28: Operating Modes

    3. Operation Operating modes Normal mode This is the standard operating mode, set by default in the factory. Under normal condition (Normal AC source available): LED (1) is ON. LEDs (2), (3), (4) are green. The equipments are protected by the UPS.
  • Page 29: Ups Shutdown

    3. Operation UPS shutdown 1 - Press the "0" button (1) more than 3s. The buzzer beeps once, and the load is no longer protected by the UPS. It is powered via the Bypass AC source. If the UPS is set in frequency converter mode, the equipments will not be powered.
  • Page 30: Access To Measurements And Personalisation Data

    4. Access to measurements and personalisation data Display organisation Measurements UPS Set-up Maintenance Access to measurements Press the scroll button (see section 1.5, page 10) to access measurements for voltage, current, frequency, power output and battery capacity. Access to UPS set-up and maintenance Press the scroll button (1) a number of times to point the UPS set-up or Maintenance menu...
  • Page 31: Ups Set-Up

    4. Access to measurements and personalisation data UPS set-up Local settings Function Factory setting Options Language English French, German, Italian, Portuguese, Spanish Date / Time Format International US (MM-DD-YYYY/HH:MM AM/PM) (DD-MM-YYYY/HH :MM) Date / Time Change GMT + 1 MM-DD-YYYY/HH :MM adjustable (Continental Europe) Audible Alarm Output settings...
  • Page 32: Battery Settings

    User Batt Settings UPS reads number of From 0 to 40 Ah 5 Ah increment battery modules connected Protection against deep discharge. Deep Disch Protect If disable, EATON warranty will be void Maintenance Function Sub-Function Option / Display Comments Model...
  • Page 33: Troubleshooting

    5. Troubleshooting Troubleshooting LEDs If LED (1) is ON: the equipments are protected by the UPS but the operation is downgraded. If LED (2) is ON: the equipments are no longer protected by the UPS. Press the escape button (3) to stop the audible alarm.
  • Page 34: System Diagnosis Fault

    5. Troubleshooting System diagnosis fault A internal sub-module fault is detected A internal power sub-module (1) fault is detected. Press the "Enter" button (2). Choose one of the two sequences below: Start with xUPS You can even run the UPS with a reduced power rate Press the scroll button (3).
  • Page 35: Environment Faults

    Check if the power rate of the power sub-module COMPATIBLE compatible. is 5 kVA. SOFT FRAME POWER The software of the power sub-module Upgrade the UPS software via www.eaton.com NOT COMPATIBLE is not compatible with the Mx Frame software 34008486EN/AC Page 36...
  • Page 36: Internal Faults

    5. Troubleshooting Internal faults Display Signification Correction POWER MODULE FAULT Internal power sub-module fault detected. Call the after-sales support department. Use "Enter" button (1) to display details. Follow the power sub-module replacement procedure (see section 7.1 page 39) BATT MODULE FAULT Battery fault detected during the battery Call the after-sales support department.
  • Page 37: Life Cycle Monitoring (Lcm)

    : LCM warning details Signification BATTERY CHECK RECOMMENDED Battery is approaching its reliability end of life. Risk to reduce CONTACT EATON AT dramatically backup time www.eaton.com Reset or disable LCM In case of any LCM messages displayed:...
  • Page 38: Maintenance

    3 - Pull the battery sub-module slightly, then lift it to extract it. Reconnecting the battery sub-module : Carry out the above instructions in reverse order. To ensure safety and high performance, use only batteries supplied by EATON. 34008486EN/AC - Page 39...
  • Page 39 7. Maintenance Service position (bypass position) This operation must be carried out by qualified electrical personnel only. The equipments should be powered via the Normal AC source, and not protected by the UPS. 1 - Press and hold the (0) (OFF) button (1) for 3 seconds/ The load is powered via the Bypass AC source (bypass mode).
  • Page 40: Service Position (Bypass Position)

    7. Maintenance Normal position (online mode) This operation must be carried out by qualified electrical personnel only. Return to normal position from service position (bypass position). 1 - Push the red padlock in the center of the manual bypass switch (1) to unlock it NORMAL 2 - Set the bypass switch (1) to test position.
  • Page 41: Training Centre

    7. Maintenance Training centre To fully master operation of your EATON product and carry out level 1 servicing, see our complete range of technical training courses, available in both French and English. For further information, please visit our website: www.eaton.com...
  • Page 42: Appendices

    8. Appendices Technical specifications MX Frame 15000 RT MX Frame 20000 RT MX EXB Output power 15 kVA 20 kVA 13.5 kW 18 kW Electrical supply network Rated input voltage Single phase 230 V / Three phase 400 V Input voltage range...
  • Page 43: Glossary

    It is possible to modify certain UPS parameters set in the factory. Certain UPS functions Personalisation can also be modified by the EATON power management products to better suit user needs. Programmable These outlets can be automatically shut down during operation on battery power...