Powerware Series
®
®
Eaton FERRUPS
FE/QFE UPS
Installation Guide

Advertisement

Table of Contents
loading

Summary of Contents for Eaton FerrUPS FE

  • Page 1 Powerware Series ® ® Eaton FERRUPS FE/QFE UPS Installation Guide...
  • Page 2 Eaton Corporation or its subsidiaries and affiliates. All other trademarks are property of their respective companies. ECopyright 2000–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
  • Page 3: Table Of Contents

    ............Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 4 TABLE OF CONTENTS Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 5: Introduction

    If you purchased an external battery cabinet, an electrician must wire the battery to the UPS as described in Chapter 7, “External Battery Cabinet Installation.” Continue to the startup section in the Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) User's Guide. Hardwired Installation...
  • Page 6 Battery Cabinet Installation” for wiring connections. Complete the phase check as described in Chapter 8, “Phase Check.” Continue to the startup section in the Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) User's Guide. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 7: Safety Warnings

    Proper disposal of batteries is required. Refer to your local codes for disposal requirements. Never dispose of batteries in a fire. Batteries may explode when exposed to flame. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 8 Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for bortskaffelsesprocedurer. Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere ved åben ild. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 9: Belangrijke Veiligheidsinstructies

    Volg de desbetreffende aanwijzingen op. De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke voorschriften. Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 10 Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketään oikosulkuun. Noudata asianmukaisia ohjeita. Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä. Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 11 Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité. Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire exploser. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 12 Verbrennungen verursachen. Die entsprechenden Vorsichtsmaßnahmen sind unbedingt zu beachten. Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen Bestimmungen zu beachten. Batterien niemals verbrennen, da sie explodieren können. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 13 õøçëü ñåýìá âñá÷õêõêëþìáôïò. ËáìâÜíåôå ôéò êáôÜëëçëåò ðñïöõëÜîåéò. Áðáéôåßôáé óùóôÞ äéÜèåóç ôùí óõóóùñåõôþí. Äåßôå ôïõò ôïðéêïýò êáíïíéóìïýò ðïõ áöïñïýí ôéò áðáéôÞóåéò äéÜèåóÞò ôïõò. ÐïôÝ ìçí ðåôÜôå ôïõò óõóóùñåõôÝò óôç öùôéÜ, ãéáôß ìðïñåß íá åêñáãïýí. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 14: Avvisi Di Sicurezza

    Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare riferimento alle disposizioni locali. Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 15: Viktig Sikkerhetsinformasion

    Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av batterier. Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 16 Siga as instruções apropriadas ao desfazer‐se das baterias. Consulte os códigos do local para maiores informações sobre os regulamentos de descarte de produtos. Nunca jogue as baterias no fogo, porque há risco de explosão. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 17 Íåîáõîäèìî ñîáëþäàòü ïðàâèëà óòèëèçàöèè àêêóìóëÿòîðîâ. Îáðàòèòåñü ê ìåñòíûì íîðìàòèâíûì àêòàì çà èíôîðìàöèåé î òðåáîâàíèÿõ ê óòèëèçàöèè. Íèêîãäà íå áðîñàéòå àêêóìóëÿòîðû â îãîíü. Àêêóìóëÿòîðû ìîãóò âçîðâàòüñÿ ïîä âîçäåéñòâèåì îãíÿ. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 18: Advertencias De Seguridad

    Es necesario desechar las baterías de un modo adecuado. Consulte las normas locales para conocer los requisitos pertinentes. Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las expone a la llama. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 19 Batterierna kan ge elektriska stötar eller brännskador från hög kortslutningsström. Följ tillämpliga anvisningar. Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 20 SAFETY WARNINGS Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 21: Setup

    15.1I (38.5 cm) 15.2I (39.0 cm) 20.2I (51.5 cm) 1.8 kVA, 2.1 kVA, and 3.1 kVA 21.2I (54.0 cm) 15.25I (39.0 cm) 22.9I (58.5 cm) Figure 1. UPS Dimensions Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 22 49I (124.5 cm) 15I (38.5 cm) 32I (81.5 cm) ASY-0385 and ASY-0685 51I (129.5 cm) 30I (76.5 cm) 32I (81.5 cm) Figure 2. External Battery Cabinet Dimensions Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 23 BPE-04 and BPE-05 17I (43.2 cm) 12I (30.5 cm) 18I (45.7 cm) 16I (40.6 cm) 9I (22.9 cm) BPE-01 BPE-02, 04, and 05 Figure 3. External Bypass Switch Dimensions Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 24: Equipment Clearances

    12I (30.5 cm) above the UPS for proper ventilation. NOTE For 4.3–18 kVA models with an internal bypass switch, measure from the back of the switch. Figure 4. Installation and Service Clearances Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 25: Location Requirements

    High Altitude Operation: The maximum operating ambient temperature decreases 1°C per 300m above sea level (2°F per 1000 ft above sea level). Maximum elevation is 3000m (10,000 ft). Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 26 SETUP Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 27: Electrical Installation

    NOTE If you have a plug-receptacle unit, continue to “External Battery Cabinet Installation” on page 55 to install optional external battery cabinets or to the startup section in the Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) User's Guide. W A R N I N G Only qualified service personnel (such as a licensed electrician) should perform the hardwired installation.
  • Page 28: Bypass Switches

    If you turn a BBM switch from UPS to LINE, the switch disconnects the load from UPS output power before connecting the load to AC input power. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 29 Figure 5 shows a UPS with a separate external battery cabinet and an external bypass switch. Continue to Chapter 5, “External Bypass Switch Installation” on page 29 for electrical connections. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 30 External Bypass Switch Bypass Building Disconnect Switch Load Line Service Distribution Panel Panel Connect to (DC) External Batteries Figure 5. Typical Hardwired Installation with External Bypass Switch Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 31 Bypass Building Load Disconnect Switch Line Service Distribution Panel Panel Connect to (DC) if there are External Batteries Figure 6. Typical Hardwired Installation with Internal Bypass Switch Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 32 ELECTRICAL INSTALLATION Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 33: External Bypass Switch Installation

    Before you install the bypass switch, verify that the bypass switch and the AC disconnect switch are in the OFF position. Identify the installation wiring diagram that applies to your FERRUPS (see Table 9). Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 34 *With a step-up or step-down transformer. **Contact your service representative for (a) single-phase installations that do not have the same input and output voltage, or (b) split-phase installations that require 220 Vac. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 35 Mount the bypass switch within sight of the UPS. If you do not have an Eaton bypass switch with an AC disconnect switch or the fuse box or panel is out of sight, you must install a separate disconnect switch next to the UPS.
  • Page 36 Install the conduit adapters. AC Input and AC Output conductors must be run through separate pieces of conduit. UPS output circuits shall be installed in dedicated conduit systems and not shared with other electrical circuits. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 37 Use copper wire and the appropriate wire size for the current. See Figure 7 for sample terminal strip labels. BPE-01 BPE-02, BPE-04, BPE-05 Figure 7. External Bypass Switch Terminal Strip Labels Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 38: Installation Wiring Diagrams For External Bypass Switches

    NOTE 5 The customer must provide output overcurrent protection as stated in NEC Section 240-21 or local codes. Size the protection device according to local code requirements. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 39 For 120/208/240 models, connect X1 on the UPS to L1 on the bypass switch; for 208 Vac, connect the bypass switch L2 to the UPS XT1; for 240 Vac, connect the bypass switch L2 to the UPS XT2. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 40 500 VA 700 VA 850 VA 1.15 kVA 1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA 120V, Standard Charger 4.4A 5.8A 7.0A 8.4A 120V, 15A Charger 8.9A Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 41 208 Vac 240 Vac Charger 500 VA – 1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA 500 VA – 1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA Standard Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 42 Figure 10. FE 500 VA–3.1 kVA UPS with External Bypass Switch Table 15. Minimum Recommended Circuit Breakers for 240 Vac Charger 500 VA–1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA Standard Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 43 2.5A 3.8A 4.2A 4.6A 5.4A 7.5A 7.8A 4.6A 5.9A 6.3A 6.7A 7.5A 240 Vac Standard 2.4A 3.5A 4.0A 4.4A 5.2A 7.2A 7.4A 4.6A 5.7A 6.2A 6.6A 7.4A Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 44 Figure 12. FE 4.3–7 kVA UPS with External Bypass Switch Table 17. Minimum Recommended Circuit Breakers for 120 Vac Charger 4.3 kVA 5.3 kVA 7 kVA Standard Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 45 Figure 13. FE 4.3–18 kVA UPS with External Bypass Switch Table 18. Minimum Recommended Circuit Breakers for 208 Vac or 240 Vac 208 Vac 240 Vac Charger 12.5 12.5 Standard Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 46 Figure 14. FE 4.3–18 kVA UPS with External Bypass Switch Table 19. Minimum Recommended Circuit Breakers for 240 Vac Charger 4.3 kVA 5.3 kVA 7 kVA 10 kVA 12.5 kVA 18 kVA Standard Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 47 FE: 60 Hz 220 Vac Input and Output For FE 60 Hz 220 Vac, use only a BBM switch. Figure 15. FE or QFE 4.3–18 kVA UPS with External Bypass Switch Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 48 7 kVA 10 kVA 12.5 kVA 18 kVA 60 Hz Standard 220 Vac 50 Hz Standard 220 Vac 50 Hz Standard 230 Vac 50 Hz Standard 240 Vac Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 49: Internal Bypass Switch Installation

    *With a step-up or step-down transformer. **Contact your service representative for (a) single-phase installations that do not have the same input and output voltage, or (b) split-phase installations that require 220 Vac. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 50 Install the conduit adapters. AC Input and AC Output conductors must be run through separate pieces of conduit. UPS output circuits shall be installed in dedicated conduit systems and not shared with other electrical circuits. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 51 If your UPS does not have an external battery cabinet(s), continue to “Phase Check” on page 67. If your UPS has an external battery cabinet(s), continue to “External Battery Cabinet Installation” on page 55. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 52: Installation Wiring Diagrams For Internal Bypass Switches

    External UPS batteries are optional. The battery cables are connected to the DC terminals on the DIN RAIL in the UPS. See “External Battery Cabinet Installation” on page 55 for external battery cabinet installation. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 53 Figure 17. FE 4.3–7 kVA UPS with Internal Bypass Switch Table 23. Minimum Recommended Circuit Breakers for 120 Vac Charger 4.3 kVA 5.3 kVA 7 kVA Standard Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 54 Figure 18. FE 4.3–18 kVA UPS with Internal Bypass Switch Table 24. Minimum Recommended Circuit Breakers for 208 Vac or 240 Vac 208 Vac 240 Vac Charger 12.5 12.5 Standard Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 55 Figure 19. FE 4.3–18 kVA UPS with Internal Bypass Switch Table 25. Minimum Recommended Circuit Breakers for 240 Vac Charger 4.3 kVA 5.3 kVA 7 kVA 10 kVA 12.5 kVA 18 kVA Standard Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 56 FE: 60 Hz 220 Vac Input and Output For FE 60 Hz 220 Vac, use only a BBM switch. Figure 20. FE or QFE 4.3–18 kVA UPS with Internal Bypass Switch Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 57 7 kVA 10 kVA 12.5 kVA 18 kVA 60 Hz Standard 220 Vac 50 Hz Standard 220 Vac 50 Hz Standard 230 Vac 50 Hz Standard 240 Vac Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 58 INTERNAL BYPASS SWITCH INSTALLATION Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 59: External Battery Cabinet Installation

    Any battery used with this UPS shall comply with the applicable requirements for batteries in the standard for emergency lighting and power equipment, UL 924. Cabinets are designed to be used with, and batteries must be replaced with, Eaton battery number BAT-XXXX or equivalent.
  • Page 60: Before Installing The Batteries

    ANSI/NFPA 70-1993. If you are replacing batteries or repairing battery connections, follow the procedure in the Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) User's Guide to shut off your UPS and remove both AC and DC input power.
  • Page 61 UPS and the batteries, and others may have an external DC switch. FE/QFE 4.3–18 kVA models also have a DC switch behind the UPS front cover panel. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 62: Installing And Connecting The Batteries

    (30.5 cm) of the UPS because the connector or plug does not connect to flexible conduit. Install flexible conduit for battery cables according to local or national code. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 63 Do not make connections to the RS-232 communication port if the UPS is connected to a positive ground battery system. The RS-232 ground must be isolated to prevent equipment damage. For assistance, contact your service representative. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 64 If you have more than one external battery cabinet, find the battery cable assembly that will connect the external battery cabinets. Pull the cables through the conduit that you installed between the cabinets. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 65 Other batteries do not have a battery number on the top. To find the torque value for these batteries, check the battery terminal type; then, use Figure 23 to find the torque value for that terminal type. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 66 You should connect the cables to the batteries first. Refer to the battery installation diagram as you follow the steps below. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 67 UPS terminal strip; then, connect the positive ( ) cable to the positive ( ) terminal on the UPS terminal strip. Tighten the terminal connections securely. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 68 After you have checked the DC voltage, turn the DC switch on the external battery cabinet(s) to the OFF position. 14. Complete the phase check beginning on page 67. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 69: Replacing The Batteries

    Contacting any part of a grounded battery can cause a risk of electric shock. An electric shock will be less likely if you disconnect the grounding connection before you work on the batteries. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 70: Recycling The Used Battery

    Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead‐acid batteries and must be disposed of properly. For more information, contact your local recycling or hazardous waste center. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 71: Phase Check

    NOTE The AC LINE indicator does not illuminate for FE 500 VA–3.1 kVA models with serial numbers 25000 and greater until the UPS ON/OFF switch is turned to the ON position. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B...
  • Page 72 After a short startup test, the READY indicator blinks for a few seconds and then remains illuminated. The UPS is ready to supply output power. Turn the bypass switch to the UPS position. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 73 AC Line Input Measurement Output 7 to 8* 11 to 12 6 to 7 10 to 11 6 to 8* 10 to 12 *60 Hz, 208 or 240V only. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 74 5 to 8 External Bypass Switch (BPE-02, BPE-04, or BPE-05) 6 to 10* 8 to 12** *60 Hz, 208 or 240V only. **60 Hz, 120V or 50 Hz, 220/230/240V. Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...
  • Page 75 20. The equipment will not be protected by the UPS until you start up the UPS and turn the bypass switch to the UPS position. Refer to the startup section in the Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) User's Guide.
  • Page 76 PHASE CHECK Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide 164201403 Rev B www.eaton.com/powerquality...