Cable Connection Precautions - Huawei PDU8000-0125DCV8-BXA006 User Manual

Bcb box
Table of Contents

Advertisement

PDU8000-(0125, 0250, 0400, 0630) DCV8-BXAXXX
BCB Box
User Manual
Terminal
UPS-
BAT+
BAT-
PE
The following table lists the torque for securing bolts in the BCB box.
Table 3-5 Torque for securing bolts
Bolt Specifications
M6
M8
M10
M12
M16

3.2.4 Cable Connection Precautions

Issue 01 (2019-03-07)
Number of
Terminals and
Hole Diameter
2 x M12
(through-hole)
2 x M12
(through-hole)
2 x M12
(through-hole)
1 x M12
(through-hole)
The recommended cable specifications are for reference only. Prepare cables based on site requirements.
Copyright © Huawei Technologies Co., Ltd.
Recommended
Recomm
Cable
ended
Specifications
Wiring
Terminal
1 x (2 x
150-M12
2
150mm
)
1 x (2 x
150-M12
2
150mm
)
1 x (2 x
150-M12
2
150mm
)
2
1 x 150mm
150-M12
Torque (N.m)
5
13
27
47
120
3 Installation
Recommend
Reco
ed Bolt
mmen
Specificatio
ded
ns
Cable
Color
2 x (M12 x
Black
45)
2 x (M12 x
Red
45)
2 x (M12 x
Black
45)
M12 x 45
Green-
and-yel
low
13

Advertisement

Table of Contents
loading

Table of Contents