Specifications - INFOSEC UPS SYSTEM E4 Pro One Series User Manual

Table of Contents

Advertisement

Available languages

Available languages

6. Specifications

* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC or when UPS is operated in
parallel.
**When using 16 pieces of batteries, the output power factor will be derated to 0.8. If using 18 or 19 pieces of batteries, the output power
factor will be derated to 0.9.
***If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
Product specifications are subject to change without further notice.
INFOSEC UPS SYSTEM – 15, Rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
67
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 10 19 AA AA 205 28

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the E4 Pro One Series and is the answer not in the manual?

Questions and answers

Table of Contents