11 Supplement
F
= √(0.26 %)
+ (0.1 %)
2
perf
F
= 0.28 %
perf
- 2. step: Total deviation F
F
= F
+ F
total
perf
stab
F
= 0.28 % (result of step 1)
perf
F
= (0.05 % x TD)
stab
F
= (0.05 % x 2.5)
stab
F
= 0.13 %
stab
F
= 0.28 % + 0.13 % = 0.41 %
total
The total deviation of the measuring system is hence 0.41 %.
Deviation in mm: 0.41 % of 1600 mm = 7 mm
The example shows that the measurement error in practice can be considerably higher than the
basic accuracy. Reasons are temperature influence and Turn down.