Fig. 32: F
through thermal change current output, in this example = 0.1 %
a
F
= √(0.45 %)
+ (0.1 %)
2
total
The total deviation of the measuring system is hence 0.46 %.
Deviation in mm: 0.46 % of 12000 mm = 55 mm
The example shows that the measurement error in practice can be considerably higher than the
basic accuracy. Reasons are temperature influence and Turn down.
The thermal change of the current output is in this example is nearly small.
9.4
Dimensions
The following dimensional drawings represent only an extract of the possible versions. Detailed
dimensional drawings can be downloaded at www.vega.com under " Downloads" and " Drawings".
VEGABAR 83 • Secondary Device for electronic differential pressure
0,3 %
0,15 %
-40°C
-20°C
-0,15 %
-0,3 %
)= 0.46 %
2
40°C
60°C
20°C
9 Supplement
80°C
65