6 Set up with the display and adjustment module
Lock/Unlock adjustment
Language
36
Caution:
Note the following, if the respective sensor is used as part of an over-
fill protection system according to WHG:
If a linearisation curve is selected, the measuring signal is no longer
necessarily linear to the filling height. This must be considered by the
user especially when setting the switching point on the limit signal
transmitter.
In the menu item "Lock/unlock adjustment" you safeguard the sensor
parameters against unauthorized or unintentional modifications.
This is done by entering a four-digit PIN.
With active PIN, only the following adjustment functions are possible
without entering a PIN:
Select menu items and show data
Read data from the sensor into the display and adjustment module
Releasing the sensor adjustment is also possible in any menu item by
entering the PIN.
Caution:
With active PIN, adjustment via PACTware/DTM and other systems is
also blocked.
6.5.2 Display
This menu item enables the setting of the requested national lan-
guage.
The following languages are available:
German
English
French
Spanish
Russian
Italian
Dutch
Portuguese
Japanese
Chinese
VEGABAR 86 • Foundation Fieldbus