Computer SMART III FAST
Lo
The
value: when the unit exceeds this value for 30 minutes, alarm
E11
if alarm
is enabled
activates alarm
HI
value: if the unit exceeds this value for 30 seconds, alarm
The
E12
alarm
is enabled, the Computer SMART III FAST unit enters the Disconnection status and
activates alarm
If the unit falls back under the
normal operating status.
In the No Connection status, the unit does not connect the stages, but also does not disconnect them
if the operation requires it.
In the Disconnection status, it disconnects all the stages and does not allow them to connect.
The
key increases the digit value.
The
key decreases the digit value.
The
key skips to the previous digit and the
Press
to validate the data; the
Lo
HI
Value and
Value:
Maximum value: 9999.
Minimum value: 1
If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the unit switches to the simulation screen,
.
SCREEN"
Instruction Manual
,
the Computer SMART III FAST unit enters No Connection status and
E11
.
E12
.
Lo
value for 10 minutes, it deactivates the alarms and returns to the
symbol disappears from the display.
E09
key skips to the next digit.
E09
is triggered, and
is triggered, and if
"5.30.- SIMULATION
99