Dc Connections From The Pv Array; Dc Wiring - Solectria Renewables PVI 23TL Installation And Operation Manual

Table of Contents

Advertisement

PVI 23TL & PVI 28TL Installation and Operation Manual 
 
5.0  DC Connections from the PV Array 
 
WARNING:  All  wiring  connections  at  the  inverter  must  be  performed  with  the 
building  AC  source  circuit  panel/breaker  off  and  the  PV  module  strings 
disconnected. AC and DC disconnect switches at the inverter must also remain off 
during termination. 
 
WARNING: All electrical wiring must be done by electrically qualified personnel in 
accordance to local and national electrical code. 
 
WARNING: Remove all fuses. Before connecting the DC conductors of the PV array 
to the inverter, verify and mark the polarity of the conductors. Verify the correct 
polarity and voltage before installing fuses. 
 
WARNING:  Before  connecting  the  DC  conductors  of  the  PV  array  to  the  inverter 
fuse terminal or bypassing them, verify that the DC voltage is less than 1000VDC in 
all conditions. DC voltages over 1000VDC will damage the inverter. Configure the 
array  such  that  the  open  circuit  voltage  will  never  exceed  1000VDC.  Warranty  is 
void if more than 1000VDC is applied to the DC section of the inverter. 
 
WARNING:  Fuses  in  the  inverter  must  only  be  replaced  with  the  same  type  and 
rated fuses as originally installed. 
 
WARNING:  The  terminal  is  rated  only  for  CU  wire;  using  AL  wire  directly  at  the 
terminal  will  void  the  warranty.  The  use  of  AL  wire  must  follow  local  code 
requirements for connecting AL wire to CU terminals. 
 
5.1 
DC Wiring 
For DC wiring, 90°C PV copper conductors must be used. The inverter terminals are listed for 75
wire; see NEC 310.10 or the Canadian Electrical Code regarding the temperature ratings of wire 
and  terminals.  The  conductor  size  shall  not  be  smaller  than  the  75°C  wire  size  based  on  the 
ampacities given in Table 310.16 of the NEC, ANSI/NFPA 70, and an additional derating factor of 
125% as indicated by UL 1741.  
 
A maximum of 16 total DC conductors (8 positive & 8 negative) can be connected and fused at 
15Amps as shown in Figure 5.1 below.  
 
WARNING:  The  DC  input  order  has  changed  in  this  wiring  box  design  from 
previous designs,  the new order from Left to Right is DC input Positive 1, DC input 
Positive 2, DC Input Negative 1, and DC input Negative 2. 
DOCR‐070365‐E 
 
  
 
PVI Series Inverters 
°
Page 24 of 57 