Controlling All Units At A Time - HMS Networks Intesis INKNXMHI048O000 User Manual

Gateway for integration of mitsubishi heavy industries air conditioning systems into knx tp-1 (eib) control systems
Hide thumbs Also See for Intesis INKNXMHI048O000:
Table of Contents

Advertisement

KNX – Mitsubishi Heavy Industries AC
TM
Intesis
CompressorStatus
FilterSignReset
RemoConErrorReset
ThermoOnOff

Controlling all units at a time

2.2.2
Property
HW Error Com
OnOff_All
Mode_All
Mode_All::Cool
Mode_All::Heat
Mode_All::Fan
Mode_All::Auto
SetPoint_All
Fan Speed_All
FanSpeed_All::Low
FanSpeed_All::Mid
FanSpeed_All::High
FanSpeed_All::Powerful
RemoconLock_All
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
1 – Switching (1bit)
R
1 – Switching (1bit)
W
1 – Switching (1bit)
W
1 – Switching (1bit)
R
EIS type
1 – Switching (1bit)
1 – Switching (1bit)
14 – Counter (8bit)
DPT 20.105 (8bit)
DPT 1.100 (1bit)
1 – Switching (1bit)
1 – Switching (1bit)
1 – Switching (1bit)
1 – Switching (1bit)
5 – Float (2byte)
14 – Counter (8bit)
1 – Switching (1bit)
1 – Switching (1bit)
1 – Switching (1bit)
1 – Switching (1bit)
1 – Switching (1bit)
Compressor Status
0 – Off, 1 - On
Filter Sign Reset
1 – Clear Filter Alarm (When reading always 0)
Remote Controller Error Reset
1 – Clear Filter Alarm (When reading always 0)
Thermo On/Off Status (Inverter Type Only)
0 – Off, 1 - On
Signal
type
(R/W)
HW Communication Status
R
0 – Communication OK, 1 – Communication ERROR
R/W
R/W
0 – Auto, 1 – Heat, 2 – Cool, 3 – Fan, 4 – Dry
R/W
0 – Auto, 1 – Heat, 3 – Cool, 9 – Fan, 14 – Dry
R/W
R/W
0–Inactive, 1–Active
R/W
0–Inactive, 1–Active
R/W
0–Inactive, 1–Active
R/W
0–Inactive, 1–Active
Set Point Temperature (only integer numbers allowed)
R/W
R/W
0 – Low, 1 – Medium, 2 – High, 3 – Powerful
R/W
0–Inactive, 1–Active
R/W
0–Inactive, 1–Active
R/W
0–Inactive, 1–Active
R/W
0–Inactive, 1–Active
Remote Controller Lock/Unlock
W
User's Manual r1.2 eng
Description / Status
Indoor Unit On/Off
0 – Off, 1 – On
Operation Mode
Operation Mode
Operation Mode
0 – Cool, 1 – Heat
Only one of these objects will be
set / read to "1" at the same time
(all objects will be updated on bus
upon a Mode change)
16..30 ºC
Fan Speed
Only one of these objects will be
set / read to "1" at the same time
(all objects will be updated on bus
upon a FanSpeed change)
0 – Unlock, 1 - Lock
URL
https://www.intesis.com
11 / 26