Communication Objects Per Each Indoor Unit - HMS Networks Intesis INKNXMHI048O000 User Manual

Gateway for integration of mitsubishi heavy industries air conditioning systems into knx tp-1 (eib) control systems
Hide thumbs Also See for Intesis INKNXMHI048O000:
Table of Contents

Advertisement

KNX – Mitsubishi Heavy Industries AC
TM
Intesis

2.2.1 Communication objects per each indoor unit:

Property
Communication Error
OnOff
Mode
Mode::Cool
Mode::Heat
Mode::Fan
Mode::Auto
Mode::Dry
SetPoint
Fan Speed
FanSpeed::Low
FanSpeed::Mid
FanSpeed::High
FanSpeed::Powerful
RemoConLock
Louver
Room Temp
Filter Sign
ErrorCode
1
During transition between positions, Swing signal will turn on indicating the Louver is moving
2
See list of indoor unit error codes and their meaning in section 9.
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
Signal
EIS type
type
(R/W)
1 – Switching (1bit)
R
1 – Switching (1bit)
R/W
14 – Counter (8bit)
R/W
DPT 20.105 (8bit)
R/W
DPT 1.100 (1bit)
R/W
1 – Switching (1bit)
R/W
1 – Switching (1bit)
R/W
1 – Switching (1bit)
R/W
1 – Switching (1bit)
R/W
1 – Switching (1bit)
R/W
R/W
5 – Float (2byte)
14 – Counter (8bit)
R/W
1 – Switching (1bit)
R/W
1 – Switching (1bit)
R/W
1 – Switching (1bit)
R/W
1 – Switching (1bit)
R/W
1 – Switching (1bit)
R/W
14 – Counter (8bit)
R/W
5 – Float (2byte)
R/W
1 – Switching (1bit)
R
10 – Counter (16bit)
R
Description / Status
Communication Status
0 – Communication OK, 1 – Communication ERROR
Indoor Unit On/Off
0 – Off, 1 – On
Operation Mode
0 – Auto, 1 – Heat, 2 – Cool, 3 – Fan, 4 – Dry
Operation Mode
0 – Auto, 1 – Heat, 3 – Cool, 9 – Fan, 14 – Dry
Operation Mode
0 – Cool, 1 – Heat
0 – Inactive, 1 – Active
0 – Inactive, 1 – Active
0 – Inactive, 1 – Active
0 – Inactive, 1 – Active
0 – Inactive, 1 – Active
Set Point Temperature (only integer numbers allowed)
16..30 ºC
Read/Write: If the option of virtual ambient temperature
and SetPoint is deactivated (see in section 4.2.1of this
document).
Write: If the option of virtual ambient temperature and
SetPoint is activated, to be configured from extern KNX
sensor (see in section 4.2.1of this document).
Fan Speed
0 – Low, 1 – Medium, 2 – High, 3 – Powerful
0 – Inactive, 1 – Active
Only one of these objects will be
set / read to "1" at the same
0 – Inactive, 1 – Active
time
0 – Inactive, 1 – Active
on bus upon a FanSpeed change
0 – Inactive, 1 – Active
Remote Controller Lock/ Unlock
0 – Remote Controller Locked, 1 – Remote Controller
Unlocked
Louver Control
1
0 – Swing, 1 – Pos1, 2 – Pos2, 3 – Pos3, 4 – Pos4
Ambient Temperature (only integer numbers)
Read: 10ºC to 40ºC
Read: If the option of virtual ambient temperature and
SetPoint is deactivated (see in section 4.2.1of this
document).
Write: If the option of virtual ambient temperature and
SetPoint is activated, to be measured from extern KNX
sensor (see in section 4.2.1of this document).
Filter Sign Status
0 – Off, 1 - On
Error Code
0 – No Error, 1..99 – Error Code
User's Manual r1.2 eng
Only one of these objects will
be set / read to "1" at the
same time (all objects will be
updated on bus upon a Mode
change)
all objects will be updated
(
2
URL
https://www.intesis.com
10 / 26
)