Mains Connection Pc1001; Fig. 4: Pc1001-A3 Mains Connector With Pre-Assembled Wiring; Table 1: Pc1001-A3 Mains Connector - 'X100 - Siemens Cerberus PACE Compact Installation, Mounting

Public address and controlled evacuation
Hide thumbs Also See for Cerberus PACE Compact:
Table of Contents

Advertisement

4.5.1 Mains connection PC1001

Pin
Designator Connection
1
L1
2
L1
3
N
4
N
5
PE
6
PE
7
PE
8
PE
9
PE
10
PE
11
PE
12
PE
A6V11899867_en--_a
The 230 V mains connector of the 'Voice alarm panel Compact 400' PC1001-A3 is
in the upper right of the cabinet. The power supply and the PE in the cabinet are
already pre-assembled.

Fig. 4: PC1001-A3 mains connector with pre-assembled wiring

Connection to the power supply; pre-assembled
PE connection to the cabinet; pre-assembled
'X100'
Terminal block for the mains supply connection
Mains connector - 'X100'
Outer conductor
Outer conductor
Neutral conductor
Neutral conductor
Protective conductor
Protective conductor
Protective conductor
Protective conductor
Protective conductor
Protective conductor
Protective conductor
Protective conductor

Table 1: PC1001-A3 mains connector - 'X100'

Follow the steps below to wire the mains supply line:
1. Connect the protective conductor with the yellow/green wire to the free 'PE'
ground terminal.
2. Connect the blue neutral conductor to the terminal 'N'.
3. Connect the brown outer conductor to the terminal 'L1'.
Wire the mains supply line
Color
Description
Brown
Mains connection
Brown
Pre-assembled; power supply
Blue
Mains connection
Blue
Pre-assembled; power supply
Yellow/green
-
Yellow/green
Pre-assembled; power supply
Yellow/green
-
Yellow/green
Pre-assembled; cabinet
Yellow/green
-
Yellow/green
-
Yellow/green
Mains connection
Yellow/green
Pre-assembled; cabinet
Mounting/Installation
31 | 122
4

Advertisement

Table of Contents
loading

Table of Contents