7.4.4 Connect PACE-Net Ethernet

7.4.5 Analog audio inputs

7.4.6 Analog audio outputs

A6V11899867_en--_a
The PT2002-A1 provides 2 Ethernet sockets at the PT2001-A1 mother board.
Always connect port A (ETH A) with an Ethernet switch.
A redundant Ethernet connection can also be established by connecting socket
port B (ETH B) with an Ethernet switch. It can be the same switch or, for higher
redundancy, another Ethernet switch in the system. If the connection on port A fails,
the PT2002-A1 uses automatically port B for the communication.
The PT2002-A1 provides 2 analog audio inputs:
Analog audio input 1 is used for the attached handheld microphone.
Analog audio input 2 can be used for other audio sources.
Analog audio input 1 and 2 connector - 'CN1'
Pin
Description
1
GND
2
Signal +
3
Signal -

Table 84: PT2002-A1 analog audio input 1 and 2 connector - 'CN1'

The PT2002-A1 provides 2 analog audio outputs:
Analog audio output 1 is used for the mounted speaker.
Analog audio output 2 can be used for other audio devices
Analog audio output 1 and 2 connector - 'CN5'
Pin
Description
1
GND
2
Signal +
3
Signal -

Table 85: PT2002-A1 analog audio output 1 and 2 connector - 'CN5'

Connect external components
Fire brigade call station (AT) PT2002-A1
Remark
-
-
-
Remark
-
-
-
7