Fig. 58: Pt2002-A1 Redundant Power Supply From A Cabinet - Siemens Cerberus PACE Compact Installation, Mounting

Public address and controlled evacuation
Hide thumbs Also See for Cerberus PACE Compact:
Table of Contents

Advertisement

7
Connect external components
Fire brigade call station (AT) PT2002-A1
7.4.3.2 Redundant power supply from a cabinet
104 | 122
Cabinet
1
3
DC 24 V
DC/DC
Ground Fault
PCA2001
PCA2011
PCA2018

Fig. 58: PT2002-A1 redundant power supply from a cabinet

1
Cerberus PACE Compact cabinet
2
External 'Fire brigade call station (AT)' PT2002-A1 with accessories
3
DC/DC converter 'MeanWell SD-50B-24 DC/DC' PCA2011-A1 or 'MeanWell
SD-100B-24 DC/DC' PCA2018-A1
4
'Ground fault monitoring (24V)' PCA2001-A1
5
Fuse 1 A
'Call station interface (redundant)' PTO2009-A1. See Call station interface
6
(redundant) PTO2009 [➙ 118].
7
DC 24 V wiring to 'Fire brigade call station (AT)' PT2002-A1 or other devices
A ground fault monitor PCA2001-A1 must be used when the PT2002-A1 is
powered from a cabinet with a DC/ DC converter PCA2011-A1 or PCA2018-A1.
If the DC 24 V is used for other external devices, a 1 A fuse is required for each
device.
A PTO2009-A1 must be used to connect the PT2002-A1 with 2 separate DC 24 V
cables from one cabinet or different cabinets. Each DC 24 V cable requires a 1 A
fuse mounted in the cabinet.
1
1
4
1
Fuse
5
1
Fuse
5
1
7
1
DC 24 V
Interf.
DC 24 V
Redund.
7
1
PTO2009
PT2002
A6V11899867_en--_a
2
1
6
1