Pioneer CB009GMFILCFHD Service Manual page 70

3d dc inverter heat pump
Table of Contents

Advertisement

Adopt suitable pipe diameter
Adopt nearby condensate water discharge
12.5.2 Key points of drainage water pipe
installation
1.
Considering the pipeline route and
elevation
Before installing condensate water pipeline,
determine its route and elevation to avoid
intersection with other pipelines and ensure
slope is straight.
2.
Drainage pipe selection
The drainage pipe diameter shall not small
than the drain hose of indoor unit
According to the water flowrate and
drainage pipe slope to choose the suitable
pipe, the water flowrate is decided by the
capacity of indoor unit.
Relationship between water flowrate and
capacity of indoor unit
Capacity (x1000Btu)
12
18
24
30
36
42
48
60
According to the above table to calculate the
total water flowrate for the confluence pipe
selection.
For horizontal drainage pipe (The following
table is for reference)
Allowable
Reference
maximum
value
of
water flowrate
PVC
inner
(l/h)
pipe
diameter of
Slope
pipe (mm)
1/50
PVC25
20
39
PVC32
25
70
PVC40
31
125
PVC50
40
247
PVC63
51
473
Attention: Adopt PVC40 or bigger pipe to be the
main pipe.
Water flowrate (l/h)
2.4
4
6
7
8
10
12
14
Remark
Slope
1/100
27
For
branch
pipe
50
88
Could be used
175
for confluence
pipe
334
For Vertical drainage pipe (The following
table is for reference)
Reference
value
PVC
inner
pipe
diameter of
pipe (mm)
PVC25
20
PVC32
25
PVC40
31
PVC50
40
PVC63
51
PVC75
67
PVC90
77
Attention: Adopt PVC40 or bigger pipe to be the
main pipe.
3.
Individual design of drainage pipe
system
The drainage pipe of air conditioner shall
be installed separately with other sewage
pipe, rainwater pipe and drainage pipe in
building.
The drainage pipe of the indoor unit with
water pump should be apart from the one
without water pump.
4.
Supporter gap of drainage pipe
In general, the supporter gap of the
drainage pipe horizontal pipe and vertical
pipe is respectively 1m~1.5m (3.28~4.92ft)
and 1.5m~2.0m(4.95~6.56ft).
Each vertical pipe shall be equipped with
not less than two hangers.
Overlarge hanger gap for horizontal pipe
shall create bending, thus leading to air
block.
5.
The horizontal pipe layout should avoid
converse flow or bad flow
67
Allowable
of
maximum
Remark
water
flowrate (l/h)
220
For
pipe
410
730
1440
Could be used
2760
for confluence
pipe
5710
8280
Too long distance
Gas bag
branch