Bosch CL300 Manual page 31

Hide thumbs Also See for CL300:
Table of Contents

Advertisement

Flexible Automation
2.1.9
Fanless Operation
* Alternating means: Two adjacent inputs or outputs, respectively, should not be driven simultaneously over the
Fanless operation of the CL300 is possible under the following conditions:
Ambient temperature must not exceed 55 _C.
D
Use of NT300 Power Supply Unit only.
D
Sufficient flow of cooling air must be ensured to avoid heat accumulation.
D
Central and parallel expansions are possible, but units must not be stacked.
D
Intelligent modules, AG/DZ, and analog input/output modules are not permit
D
ted.
I/O modules must be installed on the right−hand side of the central process
D
ing unit. All input modules come first, followed by all output modules.
The following I/O modules may be used:
D
Input Modules 24 V DC:
With 32 inputs and simultaneity factor = 0.5, alternating *
D
With 16 inputs and simultaneity factor = 0.5, alternating *
D
Output Modules 24 V DC:
With 32 outputs, 0.2 A/output and simultaneity factor = 1
D
With 32 outputs, 0.5 A/output (see paragraph 4.4.1.2)
D
With 16 outputs, 2.0 A/output and simultaneity factor =
D
0.5, alternating *
With 8 outputs, 2.0 A/output and simultaneity factor = 1
D
. Note ,
average mean time.
Configuration
2−19