Software Description
Time Base 2 S6
Data Module S8
Bit
15
S8
Marker Remanency S10
5−16
Time base for time−controlled program execution in OM6
(factor * 10 ms, 10 min max.)
Default
inactive (0)
Example
;Factor definition in OM7
L
W
K600D,B ;Time base = 6 s
T
W
B,S6
Length and number of the data module to be copied to DB (Data Buffer)
Default
Length and number = 0
Example
;Definition of module number and module length
L
W
K01FFH,B ;DM No. = 1, Length = 256 words
T
W
B,S8
8
Module Number
Fig. 5−11 Data Module S8
Limiting (byte) address for marker remanency
Default
Byte 0−127 non−remanent (M0−M127)
Byte 128−255 remanent (M128−M255)
Example
;Definition of the marker remanency limit
L
W
K101D,B ;M101 1st marker remanent byte
T
W
B,S10
7
Module Length