ALARM ZN 1 ZONE 1 The CM704B is supplied as a PCB module and can be installed in the same cabinet as the main panel or remotely from the panel using the ZONE 2 ZN 2 encrypted, 4 wire RS485 LAN connection. The module requires only one...
Page 3
CM704B Address Configuration On Solution E and Solution 144 Panels” on page 4 for more information. Depending on the EOL resistor option selected, only one CM704B can be installed on panels with a maximum zone count of 16 zones. (Solution 16i). See “Table 2: CM704B Address Configuration On Solution 16i Panel” on page 4 for more information.
Page 4
257 to 264 257 to 272 Up to 16 x CM704B can be fitted to the Solution E panel. Up to 8 x CM704B can be fitted to the Solution 144 panel. Table 3: CM704B Address Configuration On Solution E and Solution 144 Panels When Single EOL or Alarm + Tamper EOL options have been configured the first 8 zones are available on the con- trol panel zone terminals.
Page 5
(CM720 or equivalent) Figure 2: Connection Diagram With Power Supplied By System LAN+ Powering The CM704B From An External Power Supply To power the module and sensors etc from an external power supply (CM720B or CM723B) connect the wiring as shown.
Page 7
The Solution 144 and Solution E panels also support the CM705B Universal Expander Modules. The CM705B is like having 1 x CM704B zone expander, 1 x CM710B output expander and 1 x CM720B power supply module all in one and as such each universal expander added to the system will consume the address of the corresponding single function module.