Dyt_ - Delay Timer - Siemens 353 User Manual

Process automation controller
Hide thumbs Also See for 353:
Table of Contents

Advertisement

UM353-1B

3.2.36 DYT_ - Delay Timer

DYT_ function blocks perform either an ON or OFF
output delay as determined by the TYPE configuration
parameter.
ON Delay - When input P is low (0), output O1 is low.
If P goes high (1), the elapsed timer starts and sets O1
high upon reaching the DLY TIME, provided P is still
high.
OFF Delay - When input P is high (1) the output is
high. If P goes low (0), the elapsed timer starts and sets
O1 low upon reaching the DLY TIME, provided P is
still low.
The DLY TIME is adjustable over the full range of the
display, which is 0.00000 to 999999. If the delay time is set to less than the scan time of the station, the delay time
will equal the scan time.
Output ET (elapsed time) will ramp from 0.0 to the value of DLY TIME and remain there until P resets the output.
Output RT (remaining time) equals DLY TIME - ET.
POWER UP - During a warm or a hot start, with PU LAST set to YES, the block will initialize with the
input/output states and elapsed time in effect at the instant power down occurred. A cold start, with PU LAST set to
NO, will initialize the input/output states and elapsed time to 0.
.
April 2012
OFF
ON
P
BLOCK DIAGRAM
DELAY TIMER
DYT_
ESN = 000
DELAY TIMER
Pulse Input
P
D
L Y
T
I
M
E
D e L a Y TIME (minutes)
T Y
P
E
Timer TYPE
U
P
L
A
S
T
P ower U p LAST
I
N
P
U
T
P
INPUT P
(H)
E S N
E xec. S eq. N o.
1
O1
0
DLY TIME
ET
0.0
1
O1
0
DLY TIME
ET
0.0
1
0
Function Blocks
Elapsed Time
ET
Remaining Time
RT
Output 1
O1
.............. Real
(0.0)
(S)
........................ OFF/ON (OFF)
(S)
.................. NO/YES (YES)
(S)
..........
loop tag.block tag.output
(null)
................ 001 to 250
(H)
ET
.
RT
O1
3-41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents