Installation
7.5 FACTORY CALIBRATION
Unless a special calibration is ordered, the factory calibration is as follows:
ANALOG INPUT OR OUTPUT
Analog input function blocks
Analog output function blocks
Thermocouple
RTD
Slidewire
Ohms
Millivolt
Section 11.0 provides calibration procedures that may be used to check or change factory calibration.
7-22
Table 7-2 Factory Calibration
FACTORY CALIBRATION
1 to 5 Vdc
4 to 20 mA
Type J, Upscale Break
CAL ZERO - 0°C
CAL FULL - 500°C
CAL VIEW - -3.3 to 103.3%
CAL ZERO - 0%
CAL FULL - 100%
CAL VIEW - Contact factory
CAL ZERO - 0 Ohms
CAL FULL - 5000 Ohms
CAL VIEW - Contact factory
CAL ZERO - -19.0 mV
CAL FULL - +19.0 mV
CAL VIEW - 0% TO 100%
UM353-1B