Technical Features; Quick-Start Configuration - Danfoss ERC 214 Installation Manual

Digital regulator for refrigeration and defrosting
Hide thumbs Also See for ERC 214:
Table of Contents

Advertisement

Installation guide - ERC 214

1 - Technical features

• Easy to use: the four buttons, the easy-to-read menu structure and the preinstalled application solutions guarantee
optimal usability.
• Simple installation: the 16 A relay means heavy loads can be connected directly without having to use an intermediate
relay: compressors up to 2 HP on the basis of the power factor and efficiency of the motor (over 0.65 at 230 V and over 0.85
at 115 V). A vast range of compatible sensor types and screw terminals guarantee highly flexible installation.
• Unit protection: special software functions, protecting the compressor from voltage fluctuations or high condensation
temperature, to guarantee optimal unit performance.
• Energy efficiency: defrosting on request, day/night mode and intelligent evaporator fan management guarantee
maximum energy efficiency.
2 - User interface
Button function
Press and hold down on startup
RESET FACTORY SETTINGS ("FAC" is displayed)
Press for one second: BACK
Press and hold down: PULL-DOWN
Press for one second: TEMPERATURE SETPOINT/OK
Press and hold down: MENU
Display icons
Night mode (energy saving)
Compressor on
Blinks in pull-down mode

3 - Quick-start configuration

• STEP 1: Startup
• STEP 2: Select quick-start configuration menu
Within 30 seconds of startup, press "<" BACK for 3 seconds.
The main switch "r12" is automatically set to OFF.
• STEP 3: Select the preinstalled application "o61"
The display automatically shows the application selection parameter "o61".
Press SET to select the preinstalled application.
The display shows the default value (for example "AP0", blinking).
Select the type of application by pressing UP/DOWN and then SET to confirm.
The regulator presets the parameter values on the basis of the application selected and hides any irrelevant parameters.
Tip: you can easily switch from AP0 to AP6 and therefore select the simplified parameters list by pressing the UP button
(circular list).
App
Description
App 0
None (no preset application)
App 1
Medium temperature ventilated ref. units (2 – 6 °C), with timed natural defrosting
App 2
Medium temperature ventilated ref. units (0 – 4 °C), with timed electric defrosting
App 3
Low temperature ventilated ref. units (-26 – -20 °C), with timed electric defrosting
App 4
Medium temperature ventilated ref. units (0 – 4 °C), with timed electric defrosting (on the basis of the temperature)
App 5
Low temperature ventilated ref. units (-26 – -20 °C), with timed electric defrosting (on the basis of the temperature)
App 6
None (no preset application) with simplified parameters list
• STEP 4: Select the sensor type "o06"
The display automatically shows the sensor selection parameter "o06".
Press SET to select the type of sensor.
The display shows the default value (for example "n10", blinking).
Select the type of sensor by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) then SET to confirm.
NOTE: all the sensors must by the same type.
• STEP 5: Configure output DO4 "o36"
The display automatically shows the parameter "o36" to configure the output "DO4".
Select light ("Lig") or alarm ("ALA") on the basis of the application and press SET to confirm.
The display is reset in normal display mode with the control on.
© Copyright Danfoss | Published by ADAP-KOOL | 2018.10
Press for one second: UP
Press and hold down: ON/OFF
Press for one second: DOWN
Press and hold down: DEFROSTING
Fan on
Alarm activated
Installation guide | ERC 214
Defrosting
Units (°C or °F)
DKRCE.PI.RL0.N4.02 | 2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents